17.22 Module diagnostic information via physical address - SSL-ID: 00B2h
If you read this partial list, you obtain the diagnostic record set 1 of a module in a central
rack (not for PROFIBUS DP or submodules). The diagnostic record 1 contains the 4
bytes of diagnostic data that are also in data record 0, plus module-specific diagnostics
data that describe the state of a channel or a channel group. The module is to be speci-
fied via rack and slot number.
Content Value Description
SSL_ID 00B2h Shows diagnostic record set 1 of a module.
INDEX xxyyh Here the following is to be specified via INDEX:
n xx: Number of the rack
n yy: Slot number of the module
LENTHDR xxxxh The length of the record set depends on the module.
N_DR 0001h Number of record set (1)
Information to length and structure of the diagnostic record set may be
found in the corresponding manual of your diagnosable module. The first
4 bytes correspond to the data record 0 of the module.
Ä
Chap. 17.21
‘Module diagnostic information - SSL-ID: 00B1h’ page 988
Description
Header
Record set
VIPA SPEED7
SSL System status list
Module diagnostic information via physical address - SSL-ID: 00B2h
HB00 | OPL_SP7 | Operation list | en | 18-30 990