EasyManua.ls Logo

YASKAWA VIPA SPEED7 - Page 997

YASKAWA VIPA SPEED7
1007 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SSL-ID: 01FAh
The data set includes the response time. This is the time between the request and the
start of execution. This time also includes a process input image.
INDEX
offset
Length Value Description
0 1byte 01h Number of partial list: SSL Sub ID
1 1byte xxh OB Number: statistical information for OB xx
(INDEX see above)
2 1word xxxxh reserved
4 2words xxxxxxxxh Minimum execution time: The smallest measured time
8 2words xxxxxxxxh Maximum execution time: Maximum measured time
12 2words xxxxxxxxh Last run time: Last measured time
16 2words xxxxxxxxh Average execution time: The time is determined by the last 1000 recorded
times.
20 2words xxxxxxxxh reserved
The times must be specified in
µ
s
The measurement of time starts with the first transition from Startup
to RUN.
SSL-ID: 02FAh
The data set includes the time taken to create the process image of inputs. Only relevant
for OBs which a process image is assigned.
INDEX
offset
Length Value Description
0 1byte 02h Number of partial list: SSL Sub ID
1 1byte xxh OB Number: statistical information for OB xx
(INDEX see above)
2 1word xxxxh reserved
4 2words xxxxxxxxh Minimum execution time: The smallest measured time
8 2words xxxxxxxxh Maximum execution time: Maximum measured time
12 2words xxxxxxxxh Last run time: Last measured time
16 2words xxxxxxxxh Average execution time: The time is determined by the last 1000 recorded
times.
20 2words xxxxxxxxh reserved
The times must be specified in
µ
s
The measurement of time starts with the first transition from Startup
to RUN.
Record set
Record set
VIPA SPEED7
SSL System status list
Statistics information to OBs - SSL-ID: xyFAh
HB00 | OPL_SP7 | Operation list | en | 18-30 997

Table of Contents