An alarm occurs.
Continue normal operation.
Contact your Yaskawa representative.
An error occurs during the parameter file's total check.
No Yes
Yes
No
No
Yes
Turn the power OFF and then ON.
Alarm?
Continue normal operation.
The defective XCP01 circuit
board caused the alarm.
AL-0210 (MEMORY ERROR (SYSTEM CONFIG-DATA))
An alarm occurs.
An error occurs during the system configuration data's total check.
Yes
No
Alarm?
Replace the XCP01 circuit board.
Contact your Yaskawa representative.
Continue normal operation.
The defective XCP01 circuit
board caused the alarm.
Alarm?
Initialize the parameter file.
Continue normal operation.
The destructured parameter
file caused the alarm.
Alarm?
Replace the XCP01 circuit board.
AL-0200 (MEMORY ERROR (PARAMETER FILE))