AL-0310 (VERIFY ERROR (CMOS MEMORY SIZE))
The system settings for the CMOS memory capacity differ from the actual capacity.
No
Yes
Alarm?
Continue normal operation.
Selection of the wrong CMOS
board caused the alarm.
Yes
No
Alarm?
Continue normal operation.
The defective expansion CMOS board caused the alarm.
Contact your Yaskawa
representative.
Replace the expansion CMOS board.
AL-0300 (VERIFY ERROR (SYSTEM CONFIG-DATA))
An error occurs during the check of the system configuration data and the parameter file.
An alarm occurs.
No
Yes
Alarm?
Continue normal operation.
The destructured parameter
file caused the alarm.
Yes
No
Alarm?
Continue normal operation.
The defective XCP01 circuit
board caused the alarm.
Contact your Yaskawa representative.
Initialize the parameter file.
Replace the XCP01 circuit board.
An alarm occurs.
Check the memory capacity of the expansion CMOS board.