3. Cabling
3-95
TI 33Q01J10-01E
Clamp filter
In order to enhance noise resistance, attach three clamp filters in succession at both ends of
the V net cable (10BASE-5) near to the V net couplers.
Refer to Figure for a typical mounting example.
F030810.ai
Clamp filter
Clamp filter
V net Cable (10BASE-5)
Figure Clamp filter
V net cable (10BASE-2)
• V net cable (10BASE-2)
Connection: Type BNC plug
Finished cable dimensions: ø5 mm
Connection: Type BNC plug
Impedance: 50 ohm
• V net terminator (for 10BASE-2 cable)
F030820.ai
Figure V net cable and V net terminator (for 10BASE-2 cable)
T-type connector
When the V net cable is connected, put the T-type connector between insulation sheets to
prevent it from touching other metals. The surfaces of the insulation sheets that come with
the T-type connector (2 sheets) are adhesive. The figure below shows how to attach them.
Place two pieces of insulation sheets so that the adhesive surfaces face the T-type
connector and sandwich the T-type connector between them.
Press the two pieces of insulation sheets together tightly with your fingers, making sure that
the sheets cover the metal part of the T-type connector.
F030819.ai
Insulation sheet
T-type connector
Figure Insulation Sheet
Sep. 30, 2008-00