App 2-13
IM CW120-E
Communication Commands
App
Appendix 2. Communication Commands
:COMMunicate:VERBose
Function Sets/queries whether the response
to a query is returned in full or
abbreviated form.
Syntax :COMMunicate:VERBose
{<Boolean>}
:COMMunicate:VERBose?
Example :COMMUNICATE:VERBOSE ON
:COMMUNICATE:VERBOSE?
:COMMUNICATE:VERBOSE 1
1.7.2 SYSTem Group
The commands in the SYSTem group set or
query system parameters.
:SYSTem?
Function Queries all the system settings.
Syntax :SYSTem?
:SYSTem:BACKlight
Function Sets/queries whether the LCD
backlight is set to ON or OFF.
Syntax :SYSTem:BACKlight?
:SYSTem:BACKlight
{<Boolean>}
:SYSTem:CLAMp
Function Sets/queries the type of clamp.
Syntax :SYSTem:CLAMp?
:SYSTem:CLAMp {<NRf>}
<NRf> = 0: 5 to 50 A
1: 20 to 200 A
2: 50 to 500 A
3: 200 to 1000 A
:SYSTem:CURRent?
Function Queries all the settings relating to
the current range.
Syntax :SYSTem:CURRent?
:SYSTem:CURRent:RANGe
Function Sets/queries the current range.
Syntax :SYSTem:CURRent:RANGe?
:SYSTem:CURRent:RANGe
{<NRf>}
<NRf> = 0: 5 A
1: 10 A
2: 20 A
3: 50 A
4: 100 A
5: 200 A
6: 500 A
7: 1000 A
:SYSTem:DATE
Function Sets/queries the date.
Syntax :SYSTem:DATE?
:SYSTem:DATE {<NRf1>,
<NRf2>, <NRf3>}
<NRf1> = Year: 2000 to 2099
<NRf2> = Month: 1 to 12
<NRf3> = Day: 1 to 31
:SYSTem:DISPlay?
Function Queries the screen currently
displayed.
Syntax :SYSTem:DISPlay?
<NRf> = 0: Instantaneous value or
electric energy
measurement screen
1: Wiring check
:SYSTem:KLOCk
Function Sets/queries whether the key-lock
function is set to ON or OFF.
Syntax :SYSTem:KLOCk?
:SYSTem:KLOCk {<Boolean>}
:SYSTem:RESEt
Function Executes system resetting.