App 2-14
Appendix 2. Communication Commands
IM CW120-E
Syntax :SYSTem:RESEt
:SYSTem:SCALing?
Function Queries all the settings relating to
scaling.
Syntax :SYSTem:SCALing?
:SYSTem:SCALing:CT
Function Sets/queries the CT ratio.
Syntax :SYSTem:SCALing:CT?
:SYSTem:SCALing:CT {<NRf>}
<NRf> = 1.00 to 10000.00
:SYSTem:SCALing:VT
Function Sets/queries the VT ratio.
Syntax :SYSTem:SCALing:VT?
:SYSTem:SCALing:VT {<NRf>}
<NRf> = 1 to 10000
:SYSTem:TIME
Function Sets/queries the clock.
Syntax :SYSTem:TIME?
:SYSTem:TIME
{<NRf1>, <NRf2>, <NRf3>}
<NRf1> = hour: 0 to 23
<NRf2> = minute: 0 to 59
<NRf3> = second: 0 to 59
:SYSTem:VOLTage?
Function Queries all the settings relating to
the voltage range.
Syntax :SYSTem:VOLTage?
:SYSTem:VOLTage:RANGe
Function Sets/queries the voltage range.
Syntax :SYSTem:VOLTage:RANGe?
:SYSTem:VOLTage:RANGe
{<NRf>}
<NRf> = 0: 150 V
1: 300 V
2: 450 V
:SYSTem:WIRIng
Function Sets/queries the wiring type.
Syntax :SYSTem:WIRIng?
:SYSTem:WIRIng {<NRf>}
<NRf> = 0: 1φ2W
1: 1φ3W
2: 3φ3W
3: 3φ3W
4: 3φ4W