5-1
IM CW120-E
Wiring
5
Chapter 5. Wiring
5.1 Precautions for Wiring the Circuit
under Test
WARNING
When wiring the CW120 or CW121, or when it is turned off, turn off the circuit under test. It is
highly dangerous to connect or disconnect voltage or clamp-on current probes without first
turning off the circuit under test.
Be extremely careful not to connect any voltage-mode circuit to the current input terminals or
any current-mode circuit to the voltage input terminals. Miswiring can result in not only dam-
age to the circuit under test or equipment under test but also injury to personnel.
Do not apply any input level higher than the following to the voltage or current input terminals
(the upper limit differs depending on the probe used):
Maximum allowable input (continuous)
Voltage input: 495 Vrms
Current input – for 96033 probe: 130 Arms
for 96030 probe: 250 Arms
for 96031 probe: 625 Arms
for 96032 probe: 700 Arms (1000 Arms for 5 minutes)
Input ratings for each range
Voltage input: 150/300/450 V
Current input – for 96033 probe: 5/10/20/50 A
for 96030 probe: 20/50/100/200 A
for 96031 probe: 50/100/200/500 A
for 96032 probe: 200/500/1000 A
SEE ALSO
For details, see Chapter 14, “Specifications.”
WARNING
If using an external voltage transformer (VT) or current transformer (CT), make sure the trans-
former can adequately withstand the voltage being measured. Be extremely careful not to
allow the secondary stage of the CT to become open-circuited while the CT is being electrified.
Otherwise, a high-voltage may develop on the secondary stage, causing extreme danger.
The maximum allowable input voltage range of the external control input terminals is -0.5 to
5.5 V. Do not apply voltages exceeding this range, otherwise the input circuitry may be dam-
aged. (When wiring the input terminals, ensure that you wire the right terminals.)
Do not use any probe other than the voltage probes supplied with the CW120/121 or dedicated
clamp-on current probes.
Do not use a clamp-on probe with any non-insulated conductors.