<5. Parameter Summary>
5-3
IM 01C25T01-06EN
Function Label Item Contents Default value Handling *
1
Diag Lim
EJX
Lim fDPmax Upper limit for Ratio fDP
Refer to Table 4.2.3
WG
Lim fDPmin Lower limit for Ratio fDP
Refer to Table 4.2.3
WG
Lim fSPlmax Upper limit for Ratio fSPl
Refer to Table 4.2.3
WG
Lim fSPlmin Lower limit for Ratio fSPl
Refer to Table 4.2.3
WG
Lim fSPhmax Upper limit for Ratio fSPh
Refer to Table 4.2.3
WG
Lim fSPhmin Lower limit for Ratio fSPh
Refer to Table 4.2.3
WG
Lim BlkFmax Upper limit for BlkF
Refer to Table 4.2.3
WG
Lim BlkFmin Lower limit for BlkF
Refer to Table 4.2.3
WG
Lim DPAvgmax Upper limit for DPAvg
Refer to Table 4.2.3
WG
Lim DPAvgmin Lower limit for DPAvg
Refer to Table 4.2.3
WG
Diag Mode
EJX
Diag Mode ILBD operation mode Stop, Calculation, or
Reference
WG
Diag Option
EJX
Diag Option Alarm masking WG
Diag Output
EJX
Diag Out Option Output mode of 4-20mA when
an advanced diagnostic alarm is
generated
O󰀨, Burnout, or Fall back O󰀨 WG
Diag Fixed Out Val 4-20 mA output when an advanced
diagnostic alarm is generated
3.6000 to 21.6000 mA 21.6 mA WG
Diag Period
EJX
Diag Period Sampling period per one Diag count 180 s WG
Diag
Reference
EJX
Diag Description Memo eld 32 alphanumerics WG
Ref fDP Reference value of fDP WG
Ref fDP Status Status of Reference fDP RG
Ref fSPl Reference value of fSPl WG
Ref fSPl Status Status of Reference fSPl RG
Ref fSPh Reference value of fSPh WG
Ref fSPh Status Status of Reference fSPh RG
Ref BlkF Reference value of BlkF WG
Ref BlkF Status Status of Reference BlkF RG
Ref DPAvg Reference value of DPAvg WG
Ref DPAvg Status Status of Reference DPAvg RG
Diag Ref Lim
EJX
Ref Lim fDPmin Lower limit of fDP 7.0E-10 WG
Ref Lim fSPmin Lower limit of fSPl and fSPh 1.0E-10 WG
Ref Lim BlkFmax Upper limit of BlkF 0.5 WG
Diag Supp
Count
EJX
Diag Supp Count Detection count to generate an
alarm
WG
*1: Handling:
R
=Read only,
W
=Read & Write,
M
=Method,
A
=Applicable for option code AL,
G
=Applicable for option code DG6,
D
=Applicable for di󰀨erential pressure transmitters. Do not change these parameters for pressure transmitters.
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
*4: For output signal code J, refer to the section 3.3.18.
*5: These parameters may contain adjustment values based on the customer range calibration at the factory upon shipment.
When executing “Clear P sensor trim”, P LTD and P UTD will become “0”, and P LTP and P UTP will become the value of LRV and
URV respectively.