<5. Parameter Summary>
5-5
IM 01C25T01-06EN
Function Label Item Contents Default value Handling *
1
Event
Notication
4-20mA
Event Notication
Control
HART 7
Event Notication (Enable event notication on
token-passing data link layer,
O)
O W
Device Status
Mask
HART 7
Event Masking W
Status group 1 to
10 Mask
HART 7
Ext dev status
Mask
HART 7
Device Diagnostic
Status 0 Mask
HART 7
Device Diagnostic
Status 1 Mask
HART 7
AO saturated Mask
HART 7
AO xed Mask
HART 7
Set Event
Notication Timing
HART 7
Congure Event Notication Timing Congure Event Notication
Retry Time, Event Max
Update Time and Event
Debounce Interval
M
*1: Handling:
R
=Read only,
W
=Read & Write,
M
=Method,
A
=Applicable for option code AL,
G
=Applicable for option code DG6,
D
=Applicable for dierential pressure transmitters. Do not change these parameters for pressure transmitters.
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
*4: For output signal code J, refer to the section 3.3.18.
*5: These parameters may contain adjustment values based on the customer range calibration at the factory upon shipment.
When executing “Clear P sensor trim”, P LTD and P UTD will become “0”, and P LTP and P UTP will become the value of LRV and
URV respectively.