<5. Parameter Summary>
5-9
IM 01C25T01-06EN
Function Label Item Contents Default value Handling *
1
Process
variables
Engr Disp User scaled value R
Engr Unit User set engineering unit Unit specied in Set Engr Unit
8 alphanumerics
R
Loop Current (DD)
AO (DTM)
HART 7
Loop current value
(Analog Output Current)
3.6 to 21.6 mA R
Loop Current Data
Quality
HART 7
Device variable process data
quality
Device variable process data
quality of Loop Current
Good R
Loop Current Limit
Status
HART 7
Device variable limit status Device variable limit status of
Loop Current
Not limited R
PV (DD)
Pres (DTM)
Pressure/Dierential pressure
value
R
PV (Pres) Data
Quality
HART 7
Device variable process data
quality
Device variable process data
quality of pressure
Good R
PV (Pres) Limit
Status
HART 7
Device variable limit status Device variable limit status of
pressure
Not limited R
PV Update time
period (DD)
Update time period
(DTM)
HART 7
PV (Pres) Update time period 45 ms R
% range (DD)
Pres % (DTM)
HART 7
Pressure value in % -2.50 to 110.00% R
% rnge (Percent
Range) Data
Quality
HART 7
Device variable process data
quality
Device variable process data
quality of % range (Percent
Range)
Good R
% rnge (Percent
Range) Limit Status
HART 7
Device variable limit status Device variable limit status of
% range (Percent Range)
Not limited R
SV (DD), SP (DTM) Static pressure value RD
SP % Static pressure value in % -10.0 to 100.00 % RD
SV (SP) Data
Quality
HART 7
Device variable process data
quality
Device variable process data
quality of SV (SP)
Good R
SV (SP) Limit
Status
HART 7
Device variable limit status Device variable limit status of
SV (SP)
Not limited R
SV Update time
period (DD)
SP update time
(DTM)
HART 7
SV (SP) Update time period 360 ms R
*1: Handling:
R
=Read only,
W
=Read & Write,
M
=Method,
A
=Applicable for option code AL,
G
=Applicable for option code DG6,
D
=Applicable for dierential pressure transmitters. Do not change these parameters for pressure transmitters.
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
*4: For output signal code J, refer to the section 3.3.18.
*5: These parameters may contain adjustment values based on the customer range calibration at the factory upon shipment.
When executing “Clear P sensor trim”, P LTD and P UTD will become “0”, and P LTP and P UTP will become the value of LRV and
URV respectively.