MODBUS Communication
18
TI 12A01F01-62EN
2.3.2 mA input settings (1700-)
Address Parameter Type Description
1700 Type int16 None(0), Current(1), Temperature(2),
Pressure(3)
1701, 1702 Temperature 4mA oat -40~260
1703, 1704 20mA oat -40~260
1705, 1706 Pressure 4mA oat 0.0~999.9
1707, 1708 20mA oat 0.0~999.9
1709, 1710 Damping time oat 0~3600
1711, 1712 AI upper limit oat 3.8~20.5 (Upper limit > Lower limit)
1713, 1714 AI lower limit oat 3.8~20.5 (Upper limit > Lower limit)
1715 Pressure Comp. int16 Disabled(0), Enabled(1)
2.3.3 Contact input settings (1800-)
Address Parameter Type Description
1800 Contact input1 Contact input
Type
int16 Disabled(0), Contact input Wash(1), Contact
input change range(2)
1801 Contact input
Wash
int16 S1(0), S2(1), S3(2)
1802 Contact input
change range
int16 mA1(1), mA2(2), mA3 (Ad)(3), mA4 (Ad)(4)
1803 Contact input2
(Ad)
Contact input
Type
int16 Disabled(0), Contact input Wash(1), Contact
input change range(2)
1804 Contact input
Wash
int16 S1(0), S2(1), S3(2)
1805 Contact input
change range
int16 mA1(1), mA2(2), mA3(3), mA4(4)