10 - 6 IM 4H3B1-01E
Alarm Indication When ALARM ACK-key is Pressed:
Non-Hold type: Alarm display is not affected when the ALARM ACK-key is
pressed.
Hold type: When alarm occurs, alarm indicator will start flashing. After
pressing the ALARM ACK-key, the indicator will show the status
of the alarm.
PERFORMANCE and CHARACTERISTICS
Input Resistance: more than 10M (TC, 20mV, 60mV, 200mV, 2V range)
approx. 1M (6, 20V range).
Input Source Resistance: DCV, TC input: less than 2k
RTD input: less than 10/wire. (Resistance is balanced between 3 wires)
Input Bias Current: less than 10nA (however, when burnout is specified for TC: 100nA).
Maximum Common Mode Voltage:
250VAC rms (50/60Hz)
Maximum Differential Noise Between Channels (50, 60Hz):
250VAC rms
Interference Between Channels:
120dB (Rg = 500, the deviation in case 30V is applied to another channel)
Common Mode Rejection Ratio:
120dB (50/60Hz ±0.1%, 500 imbalance between terminal and ground)
Normal Mode Rejection Ratio:
40dB (50/60Hz ±0.1%)
Insulation Resistance: each terminal to ground terminal: more than 20M (measured at 500VDC).
Dielectric Strength: power supply to ground terminal: 1500VAC(50/60Hz), 1 min
contact output terminal to ground: 1500VAC(50/60Hz), 1 min
measuring input terminal to ground: 1000VAC(50/60Hz), 1 min
between measuring input terminals: 1000VAC(50/60Hz), 1 min
(except for RTD)
REMOTE terminal to ground: 500VAC, 1mm
Hold type:
Alarm ON
Alarm OFF
Indicator BLINK
Indicator ON
Indicator OFF
‘ACK’‘ACK’
or
No action will occur when -key is pressed.
ALM indicator depends on alarm status.
Non-Hold type:
ACK