5-11
IM 04P01B01-01E
Frequently Used Setup Operations (Setting Mode)
5.2 Setting the Alarm
5
Alarm Value
• High Limit Alarm/Low Limit Alarm and Delay High Limit Alarm/Delay
Low Limit Alarm
Thefollowingvaluescanbespecied.
• For DC voltage, TC, and RTD input: Values within the measurable range in the
speciedrange(example:–2.000to2.000Vforthe2Vrange).
• For ON/OFF input (DI): 0 or 1.
• For linear scaling (1-5V, scaling, and square root): A value within –5 to 105% of
the scaling span (version 1.11 or later) except within the range of –20000 to 30000
(excluding the decimal point).
Note
For channels whose the leftmost value of the scale is set to –20000 (excluding the decimal),
the alarm value of –20000 is invalid. Set a value that is greater than or equal –19999.
• Difference High Limit Alarm/Difference Low Limit Alarm
Valuesinthemeasurablerangecanbespecied.Measurablerangerefersto
“Selectable Span Range” in the table on page 5-4.
• High Limit on Rate-of-Change Alarm/Low Limit on Rate-of-Change Alarm
Avaluegreaterthanorequalto1digitcanbespecied.Forexample,1digit
corresponds 0.001 for the 2 V range (measurable range: –2.000 to 2.000 V). The
maximumvaluethatcanbespeciedisthewidthofthemeasurablerange(4.000V
for 2 V range).
ForON/OFFinput,only“1”canbespecied.
Relay No.
The selectable relay numbers are listed below.
I01 and I02 on the /A1 option
I01, I02, I03, and I04 on the /A2 option
I01, I02, I03, I04, I05, and I06 on the /A3 option