12-4
IM MV1000-01E
Execution Errors
Code Message Explanation/Countermeasures/Ref. section
150 This action is not possible because sampling is in
progress.
Stop memory sampling and then execute.
See section 4.4
151 This action is not possible during sampling or calculating. Stop memory sampling or computation first.
See sections 4.4 and 10.4
152 This action is not possible because saving is in progress. Wait until the saving is complete.
153 This action is not possible because formatting is in
progress.
Wait until the formatting is complete.
154 Message not accepted because message limit was
reached.
The limit is 50 messages.
See section 6.4
155 The message is not written while sampling is stopped. Start memory sampling and then execute.
See section 4.4
156 There are no channels to be saved to the memory. Set the channels to be saved.
See sections 4.1 and 10.1
157 This function is not possible at this time. If the data type to be recorded is set to E+D, you cannot
change the trend interval by using the T/DIV key.
See section 5.2
158 Exceeds time deviation setting. When synchronizing the clock through remote control.
See section 1.7
159 It is outside the postscript message write-in range. Add message can be written to the past section of the
data being memory sampled.
See section 6.4
12.1 List of Messages