5-11
TI 05C01E02-01E 1st Edition : Oct. 31, 2001-00
The details of UT100 Series
communication functions need to be the
same as those of the communication
functions of the host devices to be
connected.
Parameters to be Set for Communication Functions
Parameter Name
MODBUS
communication
3: ASCII mode
4: RTU mode
2: Ladder
Protocol selection PSL
0: without sum check
1: with sum check
PC link
communication
0
Symbol
Setting Range
Default
Baud rate BPS 0: 2400, 1: 4800, 2: 9600
Parity
PRI
0: NONE
1: EVEN
2: ODD
Stop bit STP 1, 2
Data length
DLN
7, 8 (*1)
Address
ADR
1 to 99
Ladder communication
2: 9600
1: EVN
1
8
1
*1: When "2: Ladder" is selected, it is fixed to "8".
When "3: ASCII mode" is selected for MODBUS communication in protocol selection, the data
length is fixed to "7".
When "4: RTU mode" is selected, it is fixed to "8".
B(+)
A(—)
Shield
RSB (+)
RSA (—)
RSB (+)
RSA (—)
UT130/UT150 UT130/UT150
PC, or PLC
Grounding resistance of
no greater than 100Ω
Grounding resistance of
no greater than 100Ω
Terminating
resistor
220Ω
1/4 W
Terminating
resistor
220Ω
1/4 W
For UT130/UT150 connection
3
4
5
3
4
5
SG SGSG
B(+)
A(—)
Shield
RSB (+)
RSA (—)
RSB (+)
RSA (—)
UT152/UT155 UT152/UT155
PC, or PLC
Grounding resistance of
no greater than 100Ω
Grounding resistance of
no greater than 100Ω
Terminating
resistor
220Ω
1/4 W
Terminating
resistor
220Ω
1/4 W
For UT152/UT155 connection
26
27
28
26
27
28
SG SGSG
Wiring for Communication