8-8
<Toc> <Ind>
TI 05C01E02-01E 1st Edition : Oct. 31, 2001-00
Cable Specifications and Recommended Products
Recommended Terminals
Use M3.5 screw-compatible crimp-on terminals with an insulating sleeve, as shown below.
Power supply and relay contact output
600V vinyl insulated wire/cable, JIS C3307, 0.9 to 2.0mm
2
Thermocouple input
Shielded compensating lead wire, JIS C1610
RTD input
Shielded wire (3-wire), UL2482 (Hitachi cable)
Other signals
Shielded wire
7mm or less
7mm or less
φ 3.7mm φ 3.7mm
Standard Type
UT130 Terminal Arrangement (Standard Type)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
TC Input RTD Input
Measured Value (PV) Input
Universal input-selectable input type
7
8
6
7
8
+
B
b
A
RS-485
3
4
5
ALM2
ALM1
COM
RSB(+)
RSA(—)
SG
Alarm Outputs
When /AL or /HBA
is specified.
When /HBA is specified.
When /RS is specified.
Heater Current Detection Input
1
2
11
12
13
NO
COM
Relay Contact Output Voltage Pulse Output
Control Output
Specify one for the output signal type.
14
15
14
15
+
CT
CAUTION
To prevent damage to the controller,never provide 100-240V AC power
supply for power supply AC/DC 24V model (when /V24 is specified).
Power Supply
9
L
N
10
9
10
AC/DC 24V
100-240V AC
+
When /V24
is specified.
NOTE
The and stand for the polarityfor DC 24V power supply.
+