10-17
IM 05P01C31-01EN
Output(ControlandRetransmission)Functions
(Continued)
Parameter
symbol
Name
Display
level
Setting range Menusymbol
RTH
Maximum
value of
retransmission
output scale of
RET
STD
WhenRTS
=PV1,SP1,PV2,SP2,
TSP1,TSP2,PV,RSP,AIN2,orAIN4,
RTL + 1 digit to 30000
-19999 to RTH - 1 digit
Decimal point position:
WhenRTS=PV1,SP1,orTSP1,
decimal point position is same as
thatofPVinput.
WhenRTS=PV2,SP2,orTSP2,
decimal point position is same as
that of RSP input.
WhenRTS=PV,decimalpointposition
issameasthatofPVinputscale.
WhenRTS=RSP,decimalpoint
position is same as that of RSP
input scale.
WhenRTS=AIN2,decimalpoint
position is same as that of AIN2
scale.
WhenRTS=AIN4,decimalpoint
position is same as that of AIN4
scale.
OUT
RTL
Minimum
value of
retransmission
output scale of
RET
STD
O1RS
Retransmission
output type of
OUT current
output
STD Same as RTS
O1RH
Maximum
value of
retransmission
output scale of
OUT current
output
STD
WhenO1RS=
PV1,SP1,PV2,SP2,
TSP1,TSP2,PV,RSP,AIN2,orAIN4,
O1RL + 1 digit to 30000
-19999 to O1RH - 1 digit
Decimal point position:
WhenO1RS=PV1,SP1,
orTSP1,
decimal point position is same as
thatofPVinput.
WhenO1RS=PV2,SP2,orTSP2,
decimal point position is same as
that of RSP input.
WhenO1RS=PV,decimalpoint
positionissameasthatofPVinput
scale.
WhenO1RS=RSP,decimalpoint
position is same as that of
RSP input scale.
WhenO1RS=AIN2,decimalpoint
position is same as that of
AIN2 scale.
WhenO1RS=AIN4,decimalpoint
position is same as that of AIN4
scale
O1RL
Minimum
value of
retransmission
output scale of
OUT current
output
STD
10
10.11SettingRetransmissionOutputTerminal,Type,andScales