Bit-0toBit-3ofSPNumber(SP.B0toSP.B3)
The SP number can be switched using contact input. There are two methods to specify
SP number.
• Status switch 1 (Operation by keystroke or via communication is enabled depending
on the conditions.)
SPnumber
Contact status
SP.B3 SP.B2 SP.B1 SP.B0
1 OFF OFF OFF ON
2 OFF OFF ON OFF
3 OFF OFF ON ON
4 OFF ON OFF OFF
5 OFF ON OFF ON
6 OFF ON ON OFF
7 OFF ON ON ON
8 ON OFF OFF OFF
*1: “1” when the contact input is turned on and “0” when turned off.
*2: SP number can be switched by keystroke or via communication when all contact inputs of SP
.B0
to SP.B3 are turned off.
*3: SP number cannot be switched by keystroke or via communication when any contact input of
SP.B0 to SP
.B3 is turned on.
*4: The contact input is turned off when the bit of SP number is not assigned to the contact input.
*5: The immediately preceding SP number is held when all contact inputs are turned off.
• Status switch 2 (Operation by keystroke or via communication is disabled.)
SPnumber
Contact status
SP.B2 SP.B1 SP.B0
1
OFF OFF OFF
2
OFF OFF ON
3
OFF ON OFF
4
OFF ON ON
5
ON OFF OFF
6
ON OFF ON
7
ON ON OFF
8
ON ON ON
*1: “1” when the contact input is turned on and “0” when turned off.
*2: Contact input is turned off when the bit of SP number is not assigned to the contact input.
Setting Details
Parameter
symbol
Name
Display
level
Setting range Menusymbol
SP.BC
Bit changing method of
SP number
STD
0: Status switch 1
1: Status switch 2
DI.NU
12.1 Setting Contact Input Function