12-5
IM 05P01C31-01EN
ContactInput/OutputFunctions
12
Bit-0toBit-3ofPIDNumber(PN.B0toPN.B3)
The PID number can be switched using contact input. There are two methods to specify
a PID number.
• Status switch 1 (Operation by keystroke or via communication is enabled depending
on the conditions.)
PIDnumber
Contact status
PN.B3 PN.B2 PN.B1 PN.B0
1 OFF OFF OFF ON
2 OFF OFF ON OFF
3 OFF OFF ON ON
4 OFF ON OFF OFF
5 OFF ON OFF ON
6 OFF ON ON OFF
7 OFF ON ON ON
8 ON OFF OFF OFF
*1: “1” when the contact input is turned on and “0” when turned off.
*2: PID number can be switched by keystroke or via communication when all contact inputs of
PN.B0 to PN.B3 are turned of
f.
*3: PID number cannot be switched by keystroke or via communication when any contact input of
PN.B0 to PN.B3 is turned on.
*4: The contact input is turned off when the bit of PID number is not assigned to the contact input.
• Status switch 2 (Operation by keystroke or via communication is disabled.)
PIDnumber
Contact status
PN.B2 PN.B1 PN.B0
1 OFF OFF OFF
2 OFF OFF ON
3 OFF ON OFF
4 OFF ON ON
5 ON OFF OFF
6 ON OFF ON
7 ON ON OFF
8 ON ON ON
*1: “1” when the contact input is turned on and “0” when turned off.
*2: Contact input is turned off when the bit of PID number is not assigned to the contact input.
In Cascade control, PID number selection is only for Loop 1.
Setting Details
Parameter
symbol
Name
Display
level
Setting range Menusymbol
PN.BC
Bit changing method of
PID number
PRO
0: Status switch 1
1: Status switch 2
DI.NU
12.1 Setting Contact Input Function