<Toc> <2. Initial Settings>
2-11
IM 05D01B02-41E
4.
Press the
SET/ENT
key once to display the main
menu LOOP1.
loop 1 setup para
SETUP main menu
LOOP1
A/M
DISP
SET/ENT
5.
Press the key once to display the main
menu UTMD.
UT750 configuration
UTMD
A/M
DISP
SET/ENT
SETUP main menu
6.
Press the
SET/ENT
key once to display the
submenu MD.
UT mode set
SETUP sub menu
MD
A/M
DISP
SET/ENT
7.
Press the key twice to display the
submenu OUT.
output set
SETUP sub menu
OUT
A/M
DISP
SET/ENT
1st Edition : May 31,2000-00
8.
Press the
SET/ENT
key once to display the
parameter OT1 (control output type).
SETUP
A/M
DISP
SET/ENT
MENU:UTMD/OUT #1
output 1 select
OT1 = 0
9.
Press the or key to display the
required setpoint. The figure below shows
an example of setting to current output (4
to 20 mA DC).
MENU:UTMD/OUT #1
changing
output 1 select
OT1 = 2
A/M
DISP
SET/ENT
Blinks during
change.
10.
Press the
SET/ENT
key once to register the
setpoint.
SETUP
A/M
DISP
SET/ENT
MENU:UTMD/OUT #1
output 1 select
OT1 = 2
11.
Press the
SET/ENT
key for more than 3 seconds.
This returns you to the display shown at
power-on (figure below).
A/M
DISP
SET/ENT
SP :1.
-10 0 +10
0.0°C
DV

Related product manuals