5-16
<Toc> <5. Parameters>
IM 05D01B02-41E 1st Edition : May 31,2000-00
Retransmission Output Parameters
Located in: Main menu = CMLP ; Submenu = RET
Ref.2.2(1)
Ref.2.2(3)
Ref.2.2(1)
Ref.2.2(1)
Ref.2.2(3)
Ref.2.2(1)
Parameter
Symbol
Name of Parameter Setting Range and Description Initial Value User
Setting
Target Item
in CD-ROM
Retransmission
output-1 type
OFF (0): Disable
1: PV1, 2: SP1, 3: OUT1, 4: LPS loop power supply (15 V),
5: PV2, 6: SP2, 7: OUT2
Setpoints 5 to 7 are not available for single-loop control.
Retransmission output 1 is always provided via terminals 14
and 15.
In position proportional control, a valve opening signal (0%
to 100%) is transmitted if setpoint 3 is selected.
In heating/cooling control, an output value before allocation
to heating/cooling control (0% to 100%) is transmitted if
setpoint 3 is selected.
(0% to 50%: Cooling-side output; 50% to 100%: Heating-side
output)
1
Maximum value
of retransmission
output-1 scale
RET1=1, 2: RTL1 + 1 digit to 100.0% of PV input range
RET1=3: RTL1 + 1 digit to 100.0%
100.0% of PV
input range
RTH1
RET1
Minimum value
of retransmission
output-1 scale
RET1=1, 2: 0.0% of PV input range to RTH1 - 1 digit
RET1=3: 0.0% to RTH1 - 1 digit
0.0% of PV
input range
Retransmission
output-2 type
Retransmission output-2 is available when the type of control
output is not current or voltage pulse. The output is
provided via terminals 16 and 17.
OFF (0): Disable
1: PV1, 2: SP1, 3: OUT1, 4: LPS loop power supply (15 V),
5: PV2, 6: SP2, 7: OUT2
Setpoints 5 to 7 are not available for single-loop control.
In position proportional control, a valve opening signal (0%
to 100%) is transmitted if setpoint 3 is selected.
In heating/cooling control, an output value before allocation
to heating/cooling control (0% to 100%) is transmitted if
setpoint 3 is selected.
(0% to 50%: Cooling-side output; 50% to 100%: Heating-side
output)
OFF (0)
RTL1
Maximum value
of retransmission
output-2 scale
RET2=1, 2: RTL2 + 1 digit to 100.0% of PV input range
RET2=3: RTL2 + 1 digit to 100.0%
100.0% of PV
input range
Minimum value
of retransmission
output-2 scale
RET2=1, 2: 0.0% of PV input range to RTH2 - 1 digit
RET2=3: 0.0% to RTH2 - 1 digit
0.0% of PV
input range
RTH2
RET2
RTL2
Deviation Trend Parameters
Located in: Main menu = CMLP ; Submenu = TRND
Ref.6.1(3)
Ref.6.1(2)
Parameter
Symbol
Name of Parameter Setting Range and Description Initial Value User
Setting
Target Item
in CD-ROM
Deviation display band 0.0 to 100.0% of PV input range span
Permits a change in the span of deviation shown on the
front-panel deviation monitor.
1.0% of PV
input range
span
DVB1
Deviation trend scale Allows the deviation axis on the Deviation Trend operating
display to be re-scaled.
5.0% of PV
input range span
TSC1
Deviation trend scan
time
0 to 600 sec.
Allows the time axis on the Deviation Trend operating
display to be re-scaled.
5 sec.
TTM