<Toc> <5. Parameters>
5-19
IM 05D01B02-41E
● UT Mode Parameters
Located in: Main menu = UTMD ; Submenu = MD
Ref.1.1(4)
Ref.1.1(5)
Parameter
Symbol
Name of Parameter Setting Range and Description Initial Value User
Setting
Target Item
in CD-ROM
Controller mode
(UT mode)
1: Single-loop Control
For another controller mode, see User’s Manual (Reference)
(CD-ROM version).
1
PV sampling period
setting
50, 100, 200 and 500 ms
The controller restarts if any change is made to the PV sampling
period; this does not affect other parameter settings at all, however.
200 ms
SMP
UTM
Sampling period
error counter
(reading only)
0 to 30000
Shows 0 at
power-on.
SMEC
● Input-related Parameters
Located in: Main menu = UTMD ; Submenu = IN
Parameter
Symbol
Name of Parameter Setting Range and Description Initial Value User
Setting
Target Item
in CD-ROM
PV input type
(INPUT 1 terminals)
Terminals ,
and
OFF (0)
PV input unit Select the unit of PV input.
% (0): Percent F (5): Fahrenheit
C (1): Degree Celsius
- (2): No unit
IN1
Max. value of PV
input range
Set the instrument input range (RL1 < RH1).
- For temperature input -
Set the range of temperature that is actually controlled.
- For voltage input -
Set the range of a voltage signal that is applied.
The scale across which the voltage signal is actually controlled
should be set using the parameters Maximum Value of PV Input
Scale (SH1) and Minimum Value of PV Input Scale (SL1).
Depend on the
PV input type
Depend on the
PV input type
Depend on the
PV input type
UNI1
RH1
Min. value of PV
input range
PV input decimal
point position
(shown when in
voltage-input mode)
Set the position of the decimal point of voltage-mode PV input.
0 to 4
0: No decimal place, 1: One decimal place,
2 to 4: two, three, four decimal places
Depend on the
PV input type
Depend on the
PV input type
Depend on the
PV input type
RL1
Max. value of PV
input scale
(shown when in
voltage-input mode)
Set the read-out scale of voltage-mode PV input.
-19999 to 30000, where SL1 < SH1
SDP1
SH1
Min. value of PV
input scale
(shown when in
voltage-input mode)
Selection of PV
input burnout action
Allows the PV input value to be determined as shown below in
case of PV input burnout.
• 105% of PV input range if set to “Upscale”
• -5.0% of PV input range if set to “Downscale”
OFF (0): Disable
UP (1): Upscale
DOWN (2): Downscale
Depend on the
PV input type
SL1
Presence/absence
of PV input
reference junction
compensation
Allows input compensation to be applied to thermocouple input.
OFF (0): Absent
ON (1): Present
ON (1)
BSL1
RJC1
11 12
13
Specify the type of PV input as a range code.
See “Instrument Input Range Codes” in the
“2. Initial Settings.”
1st Edition : May 31,2000-00