SEE
ALSO
For more information about fan unit, refer to:
7.7.2, “Replacing Node Fan Unit” on page 7-37
ProSafe-RS Installation Guidance (TI 32S01J10-01E)
User's manual of each device
n
Guidelines for Selecting a Power Supply Unit
Regarding the system of the Product, you must take note of the following precautions by us-
ing a power supply unit to satisfy the various requirements of the EMC regulations:
Prevent power supply problems such as power failure or short interruptions.
Protect the power supply unit against power line noise and lightning surge.
Suppress power supply harmonic current from devices.
You must consult with the power supply unit suppliers, and then select and install a suitable
power supply unit with the considerations described in the following sections.
l
Notices on Deciding the Output Capacity of Power Supply Unit
Consult with the power supply unit suppliers and decide a suitable output capacity of the pow-
er supply unit with the following considerations:
Power consumption
Power consumed in both volt-ampere (VA) and watt (W).
Device crest factor
Ratio of the peak value to the effective value of input current supplied to each device.
Device inrush current
The maximum inrush current when power is turned on.
Power failure backup time
Time required to back up the devices when power fails.
Reserve capacity
An extra power capacity for additional devices and so on.
SEE
ALSO
For more information about power consumption, rush current, and power and ground cabling, refer to:
ProSafe-RS Installation Guidance (TI 32S01J10-01E)
l
Crest Factor
The crest factor refers to the ratio of the peak value to the ef
fective value of any input current
of a device.