IMPORTANT
Note the following points when using optical ESB bus repeater modules.
The optical ESB bus repeater master module and the optical ESB bus repeater slave
module both connected to ESB bus1 must be mounted on the odd-numbered slots. The
Optical ESB bus repeater master module and the optical ESB bus repeater slave module
both connected to ESB bus2 must be mounted on the even-numbered slots.
Be sure to put a dummy cover (SDCV01) on each slot with no module.
SEE
ALSO
For more information about restrictions on optical ESB bus repeater module installation, refer to:
Model SNT10D Unit for Optical Bus Repeater Module (GS 32Q06K11-31E)
l
Safety Control Unit (SSC60S/SSC60D, SSC50S/SSC50D, SSC10S/SSC10D)
I/O1 I/O2 I/O3 I/O4 I/O5 I/O6
Figure 3.4.2-4 Safety Control Unit (SSC60S/SSC60D, SSC50S/SSC50D, SSC10S/SSC10D)
Slots for optical ESB bus repeater modules: Slots I/O1 to I/O6
You can use slots I/O1 to I/O6. Use an odd-number slot and the next even-number slot
together.
l
Safety Node Unit (SNB10D)
I/O1 I/O2 I/O3 I/O4 I/O5 I/O6 I/O7 I/O8
Figure 3.4.2-5 Safety Node Unit (SNB10D)
Slots for optical ESB bus repeater modules: Slots I/O1 to I/O8
You can use slots I/O1 to I/O8. Use an odd-number slot and the next even-number slot
together.
<3.4 Connecting ESB Bus Cable > 3-27
IM 32Q06C10-31E 4th Edition : Jan.30,2015-00