<6. Maintenance>
6-9
IM 01C50G01-01EN
Alarm
Number
Indicator
Message
Cause
AL.117 AI4 O/S The actual mode of the AI4 block is O/S.
AL.118 SCHEDL Execution of AI1 is not scheduled.
AL.119 SCHEDL Execution of AI2 is not scheduled.
AL.120 SCHEDL Execution of AI2 is not scheduled.
AL.121 SCHEDL Execution of AI1 is not scheduled.
AL.122 STB.MAN The actual mode of the STB block is Man.
AL.130 DI1 O/S The actual mode of the DI1 block is O/S.
AL.130 DI1.MAN The actual mode of the DI1 block is Man.
AL.130 SCHEDL Execution of DI1 is not scheduled.
AL.130 DI1.SIM Simulate of the DI1 block is active.
AL.131 DI2 O/S The actual mode of the DI2 block is O/S.
AL.131 DI2.MAN The actual mode of the DI2 block is Man.
AL.131 SCHEDL Execution of DI2 is not scheduled.
AL.131 DI2.SIM Simulate of the DI2 block is active.
AL.132 DI3 O/S The actual mode of the DI3 block is O/S.
AL.132 DI3.MAN The actual mode of the DI3 block is Man.
AL.132 SCHEDL Execution of DI3 is not scheduled.
AL.132 DI3.SIM Simulate of the DI3 block is active.
AL.133 DI4 O/S The actual mode of the DI4 block is O/S.
AL.133 DI4.MAN The actual mode of the DI4 block is Man.
AL.133 SCHEDL Execution of DI4 is not scheduled.
AL.133 DI4.SIM Simulate of the DI4 block is active.
AL.134 PID1.O/S The actual mode of the PID1 block is O/S.
AL.134 PID.MAN The actual mode of the PID1 block is Man.
AL.134 SCHEDL Execution of PID1 is not scheduled.
AL.134 PID.BYP The bypass action for PID1 is active.
AL.135 PID2.O/S The actual mode of the PID2 block is O/S.
AL.135 PID.MAN The actual mode of the PID2 block is Man.
AL.135 SCHEDL Execution of PID2 is not scheduled.
AL.135 PID.BYP The bypass action for PID2 is active.
AL.136 SC O/S The actual mode of the SC block is O/S.
AL.136 SC MAN The actual mode of the SC block is Man.
AL.136 SCHEDL Execution of SC is not scheduled.
AL.137 IS O/S The actual mode of the IS block is O/S.
AL.137 IS MAN The actual mode of the IS block is Man.
AL.137 SCHEDL Execution of IS is not scheduled.
AL.138 AR O/S The actual mode of the AR block is O/S.
AL.138 AR MAN The actual mode of the AR block is Man.
AL.138 SCHEDL Execution of AR is not scheduled.
AL.150 AI1.SIM Simulate of the AI1 block is active.
AL.151 AI2.SIM Simulate of the AI2 block is active.
AL.152 AI3.SIM Simulate of the AI3 block is active.
AL.153 AI4.SIM Simulate of the AI4 block is active.
AL.154 AI1.MAN The actual mode of the AI1 block is Man.
AL.155 AI2.MAN The actual mode of the AI2 block is Man.
AL.156 AI3.MAN The actual mode of the AI3 block is Man.
AL.157 AI4.MAN The actual mode of the AI4 block is Man.
*1: Applicable only for YTA710.