Loading...
036-21106-005 Rev. B (0505)
16 Unitary Products Group
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. AC060X1224
INDOOR COIL MODEL NO. G1FA060S21,24
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 1600 1800 2000
ID DB (°F) 70 75 80 85 70 75 80 85 70 75 80 85
ID WB (°F) 57 63 67 72 57 63 67 72 57 63 67 72
75
T.C. 53.8 59.2 63.5 68.4 54.8 60.2 64.5 69.5 55.2 60.7 64.9 70.1
S.C. 45.6 42.7 44.1 43.6 47.9 45.3 46.6 46.2 49.4 46.9 48.4 47.9
KW 13.8 14.9 15.8 16.9 13.7 14.9 15.7 16.8 13.6 14.7 15.6 16.6
85
T.C. 51.6 56.8 60.9 65.7 52.5 57.7 61.8 66.6 53.0 58.2 62.2 67.1
S.C. 44.4 41.7 43.1 42.7 46.7 44.2 45.5 45.1 48.3 45.7 47.2 46.8
KW 11.8 12.7 13.5 14.4 11.7 12.7 13.5 14.4 11.6 12.6 13.3 14.2
95
T.C. 49.5 54.7 58.6 63.2 50.3 55.5 59.3 64.1 50.8 55.9 59.8 64.5
S.C. 43.2 41.0 42.0 41.8 45.5 43.2 44.5 44.2 47.1 44.7 46.3 45.8
KW 10.3 11.2 11.8 12.6 10.2 11.1 11.8 12.6 10.2 11.0 11.7 12.5
105
T.C. 47.2 52.2 55.8 60.3 47.9 52.8 56.5 60.9 48.4 53.3 56.8 61.2
S.C. 42.1 39.8 41.2 40.9 44.2 41.9 43.4 43.1 46.0 43.4 44.7 44.4
KW 8.8 9.6 10.2 10.9 8.8 9.5 10.1 10.8 8.8 9.5 10.0 10.7
115
T.C. 44.7 49.4 52.9 57.1 45.4 50.0 53.4 57.6 45.7 50.4 53.7 57.9
S.C. 40.6 38.6 39.8 39.6 43.1 40.6 41.9 41.6 44.6 42.4 43.5 43.2
KW 7.5 8.1 8.6 9.3 7.5 8.1 8.6 9.2 7.4 8.1 8.5 9.1
125
T.C. 42.3 46.7 50.1 53.9 42.9 47.4 50.4 54.4 43.4 47.8 50.9 54.6
S.C. 39.4 37.5 38.8 38.2 41.8 39.7 40.6 40.4 43.3 41.2 42.6 42.1
KW 6.3 6.9 7.3 7.8 6.3 6.9 7.3 7.8 6.3 6.9 7.3 7.7
NOTE:
ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
F3FP060 0.99 0.97 1.00
F3FV060 0.99 0.97 0.97
N1VSD20 G2FD060(S,H)24(T) 0.99 0.97 0.98
N1VSD20 G2FD061H24 1.00 0.98 0.97
N1AHD20 G2FD060(S,H)24(T) 1.00 1.00 1.00
N1AHD20 G2FD061H24 1.00 1.01 1.00
G1FA/G1UA060S21(T) 1.00 1.00 1.00
G2FD060(S,H)24(T) 1.00 1.00 1.00
G2FD061H24 1.00 1.01 1.00
G1NA060S24T 0.98 0.97 0.99
G1HD060 0.98 0.99 0.99
G1HA60S24(T) 0.99 0.98 0.99