333495-YTG-C-0908
Johnson Controls Unitary Products 19
115°F 125°F
1200
77 47.0 4.1 27.1 21.4 15.7 - - - 42.2 4.5 26.3 20.6 14.9 - - -
72 41.5 4.0 34.9 29.2 23.5 17.8 - - 36.5 4.3 34.1 28.4 22.7 17.0 - -
67 36.0 4.0 36.0 36.0 31.4 25.7 20.0 - 30.9 4.0 30.9 30.9 30.6 24.9 19.2 -
62 35.4 3.9 35.4 35.4 35.0 29.2 23.5 17.8 31.2 4.0 31.2 31.2 31.2 26.9 21.2 15.5
57 35.5 3.9 35.5 35.5 35.0 29.3 23.6 17.9 31.4 4.2 31.4 31.4 31.4 27.0 21.3 15.6
1400
77 47.1 4.6 34.7 24.0 15.7 - - - 42.6 5.0 34.9 23.8 14.7 - - -
72 41.6 4.5 37.1 30.4 23.6 16.9 - - 37.0 4.8 35.9 29.1 22.4 15.7 - -
67 36.1 4.4 36.1 36.1 31.5 24.8 18.0 - 31.3 4.6 31.3 31.3 30.1 23.4 16.6 -
62 35.5 4.3 35.5 35.5 35.1 28.4 21.6 14.9 31.6 4.6 31.6 31.6 31.6 25.3 18.6 11.9
57 35.6 4.3 35.6 35.6 35.2 28.5 21.7 15.0 31.8 4.7 31.8 31.8 31.8 25.5 18.7 12.0
1600
77 47.3 5.0 42.3 26.7 15.8 - - - 43.1 5.6 43.1 26.9 14.5 - - -
72 41.8 4.9 39.3 31.5 23.7 15.9 - - 37.4 5.3 37.4 29.8 22.1 14.3 - -
67 36.3 4.8 36.3 36.3 31.7 23.9 16.1 - 31.7 5.1 31.7 31.7 29.7 21.9 14.1 -
62 35.7 4.7 35.7 35.7 35.2 27.5 19.7 11.9 31.9 5.1 31.9 31.9 31.5 23.8 16.0 8.2
57 35.7 4.7 35.7 35.7 35.3 27.6 19.8 12.0 32.1 5.2 32.1 32.1 31.7 23.9 16.1 8.3
1800
72 42.1 5.0 40.8 33.3 24.4 15.6 - - 37.9 5.4 37.9 31.6 22.6 13.7 - -
67 36.5 4.9 36.5 36.5 32.6 23.8 14.9 - 32.1 5.2 32.1 32.1 30.4 21.5 12.5 -
62 35.9 4.8 35.9 35.9 35.7 26.8 18.0 9.1 32.4 5.2 32.4 32.4 32.2 23.2 14.2 5.3
57 36.0 4.8 36.0 36.0 35.8 26.9 18.1 9.2 32.5 5.3 32.5 32.5 32.3 23.3 14.4 5.4
2000
72 42.4 5.1 42.4 35.1 25.2 15.2 - - 38.4 5.5 38.4 33.3 23.2 13.0 - -
67 36.8 5.0 36.8 36.8 33.6 23.6 13.7 - 32.5 5.3 32.5 32.5 31.2 21.0 10.9 -
62 36.1 4.9 36.1 36.1 36.1 26.2 16.3 6.3 32.8 5.2 32.8 32.8 32.8 22.6 12.5 2.3
57 36.2 4.9 36.2 36.2 36.2 26.3 16.3 6.4 33.0 5.4 33.0 33.0 33.0 22.8 12.7 2.5
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
BHZ048 (4.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65