036-21548-001-D-0405
Unitary Products Group 13
TABLE 8: DNZ060 COOLING CAPACITIES - 5 TON
TEMPERATURE
OF AIR ON
CONDENSER COIL
AIR ON EVAPORATOR COIL
1,800 CFM 2,000 CFM
WB °F WB °F
72 67 62
57 72 67 62 57
85 °F
NET CAP. MBH 63.2 58.9 54.7 54.9 63.5 59.2 55.0 55.2
TOTAL POWER kW 5.64 5.63 5.53 5.39 5.84 5.82 5.72 5.57
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 44.9 56.1 54.7 54.9 47.7 59.2 55.0 55.2
83 39.4 50.5
54.7 54.9 41.4 53.0 55.0 55.2
80 33.9 45.0
54.7 58.2 35.2 46.7 55.0 55.2
77 28.3 39.5 49.2 52.6 28.9 40.5 48.7 48.9
74 22.8 33.9 43.6 47.1 22.7 34.2 42.4 42.6
71 -- 28.4 38.1 41.6 -- 28.0 36.2 36.4
68 -- 22.8 32.6 36.0 -- 21.7 29.9 30.1
95 °F
NET CAP. MBH 59.9 55.9 52.3 52.0 59.5 55.6 52.0 51.7
TOTAL POWER kW 6.26 6.17 6.03 5.95 6.53 6.43 6.29 6.21
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 43.9 54.9 52.3 52.0 46.6 55.6 52.0 51.7
83 38.3 49.4
52.3 52.0 40.4 51.9 52.0 51.7
80 32.8 43.9 53.1 55.1 34.1 45.6
52.0 51.7
77 27.3 38.3 47.5 49.6 27.9 39.4 45.8 45.4
74 21.7 32.8 42.0 44.0 21.6 33.1 39.5 39.2
71 -- 27.2 36.4 38.5 -- 26.8 33.2 32.9
68 -- 21.7 30.9 33.0 -- 20.6 27.0 26.7
105 °F
NET CAP. MBH 55.6 51.5 48.2 51.0 55.5 51.4 48.2 50.9
TOTAL POWER kW 6.86 6.78 6.78 6.55 7.10 7.02 7.01 6.78
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 42.2 51.0 48.2 51.0 44.9 51.4 48.2 50.9
83 36.7 47.4
48.2 51.0 38.6 49.6 48.2 50.9
80 31.1 41.8 49.9 54.0 32.4 43.5
48.2 50.9
77 25.6 36.3 44.4 48.5 26.1 37.3 41.9 44.7
74 20.0 30.7 38.8 42.9 19.9 31.0 35.7 38.4
71 -- 25.2 33.3 37.4 -- 24.7 29.4 32.2
68 -- 19.7 27.7 31.9 -- 18.5 23.1 25.9
115 °F
NET CAP. MBH 51.3 47.0 44.1 49.9 51.5 47.2 44.3 50.2
TOTAL POWER kW 7.46 7.39 7.52 7.14 7.67 7.61 7.74 7.34
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 40.5 47.0 44.1 49.9 43.2 47.2 44.3 50.2
83 35.0 45.3
44.1 49.9 36.9 47.2 44.3 50.2
80 29.4 39.8 46.8 52.9 30.7 41.4
44.3 50.2
77 23.9 34.2 41.2 47.4 24.4 35.2 38.1 43.9
74 18.4 28.7 35.7 41.8 18.1 28.9 31.8 37.7
71 -- 23.2 30.1 36.3 -- 22.7 25.6 31.4
68 -- 17.6 24.6 30.8 -- 16.4 19.3 25.1
125 °F
NET CAP. MBH 46.9 42.5 40.0 48.9 47.5 43.1 40.5 49.4
TOTAL POWER kW 8.05 8.00 8.26 7.73 8.25 8.19 8.46 7.91
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 38.8 43.0 40.0 48.9 41.5 43.1 40.5 49.4
83 33.3 43.3
40.0 48.9 35.2 44.9 40.5 49.4
80 27.8 37.8 43.6 51.8 28.9 39.4
40.5 49.4
77 22.2 32.2 38.1 46.3 22.7 33.1 34.2 43.2
74 16.7 26.7 32.5 40.7 16.4 26.8 28.0 36.9
71 -- 21.1 27.0 35.2 -- 20.6 21.7 30.6
68 -- 15.6 21.4 29.6 -- 14.3 15.5 24.4
1.
These are net capacity ratings. The indoor blower motor heat has already been subtracted from the gross cooling capacity.
ALL SENSIBLE CAPACITY