246747-YTG-L-0808
22 Johnson Controls Unitary Products
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
HIGH CFM
COOLING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATION
OUTDOOR UNIT MODEL NO. CZE03611
INDOOR COIL MODEL NO. FC/MC48C + MV16C
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 1100 1200 1300
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 34.1 36.8 36.5 38.0 39.8 34.7 37.1 36.6 37.5 39.3 35.4 37.3 36.6 37.1 38.8
S.C. 35.3 32.2 26.2 26.1 20.1 36.6 32.8 28.0 25.9 20.3 37.0 33.5 29.8 25.7 20.5
K.W. 1.9 2.0 2.1 2.0 2.0 1.9 2.0 2.1 2.0 2.1 2.0 2.0 2.0 2.0 2.1
75
T.C. 33.2 35.5 35.1 37.3 39.1 33.9 35.7 35.3 37.0 38.8 34.6 36.0 35.5 36.8 38.5
S.C. 34.5 32.0 26.3 26.1 20.3 35.6 32.7 27.9 26.3 20.5 36.8 33.4 29.4 26.5 20.7
K.W. 2.2 2.2 2.3 2.3 2.3 2.2 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.4
85
T.C. 32.4 34.1 33.8 36.5 38.5 33.1 34.4 34.1 36.5 38.4 33.8 34.6 34.3 36.5 38.3
S.C. 33.7 31.7 26.5 26.2 20.5 34.6 32.6 27.8 26.8 20.7 35.5 33.4 29.0 27.3 20.8
K.W. 2.5 2.5 2.6 2.6 2.6 2.5 2.5 2.5 2.6 2.6 2.6 2.6 2.5 2.6 2.6
95
T.C. 31.6 32.7 32.4 35.8 37.8 32.3 33.0 32.8 36.0 37.9 32.9 33.3 33.2 36.2 38.0
S.C. 32.9 31.5 26.6 26.3 20.6 33.6 32.4 27.6 27.2 20.8 34.3 33.3 28.6 28.1 21.0
K.W. 2.8 2.8 2.8 2.8 2.9 2.8 2.8 2.8 2.9 2.9 2.8 2.8 2.8 2.9 2.9
105
T.C. 29.1 30.7 30.5 33.5 34.7 29.9 30.9 30.8 33.7 35.5 30.7 31.1 31.1 33.9 36.2
S.C. 30.3 30.3 25.2 25.1 21.4 31.1 30.6 26.1 26.0 20.9 32.0 30.8 27.0 26.9 20.5
K.W. 3.2 3.2 3.2 3.3 3.3 3.2 3.2 3.2 3.3 3.3 3.3 3.3 3.2 3.3 3.3
115
T.C. 26.7 28.8 28.5 31.3 31.7 27.6 28.9 28.9 31.5 33.1 28.5 29.0 29.1 31.8 34.4
S.C. 27.7 29.1 23.8 23.9 22.1 28.8 28.8 24.6 24.8 21.0 29.8 28.4 25.4 25.7 19.9
K.W. 3.6 3.6 3.6 3.7 3.7 3.7 3.6 3.6 3.7 3.7 3.7 3.7 3.7 3.7 3.7
125
T.C. 24.2 26.9 26.6 29.0 28.8 25.3 26.9 26.9 29.4 30.7 26.3 26.9 27.2 29.6 32.7
S.C. 25.1 27.9 22.4 22.7 22.9 26.4 27.0 23.1 23.6 21.1 27.6 26.0 23.8 24.5 19.3
K.W. 4.0 4.0 4.0 4.1 4.1 4.1 4.1 4.0 4.1 4.1 4.1 4.1 4.1 4.1 4.2
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
AV36 – 0.97 0.99 1.01
AV/SV48 – 1.00 1.00 1.00
MV12B FC/MC35B 0.97 0.97 1.01
MV12B FC/MC42B 0.97 0.97 1.01
MV20D FC/MC48D 1.00 1.01 1.00
Variable Speed
Furnace
Coil
T.C. S.C. KW
PV8*B16 FC/MC/PC35B 0.98 1.00 1.01
P(C,V)9*B12 FC/MC/PC35B 0.98 0.88 1.03
PV8*C16 FC/MC/PC35C 1.00 1.01 1.00
PV8*C20 FC/MC/PC35C 1.00 1.01 1.00
P(C,V)9*C16 FC/MC/PC35C 1.00 0.94 1.01
P(C,V)9*C20 FC/MC/PC35C 1.00 0.94 1.01
PV8*B16 FC/MC/PC42B 0.98 1.00 1.01
P(C,V)9*B12 FC/MC/PC42B 0.98 0.88 1.03
PV8*C16 FC/MC/PC42C 1.00 1.01 1.00
PV8*C20 FC/MC/PC42C 1.00 1.01 1.00
P(C,V)9*C16 FC/MC/PC42C 1.00 0.94 1.01
P(C,V)9*C20 FC/MC/PC42C 1.00 0.94 1.01
PV8*C16 FC/MC/PC48C 1.00 1.01 1.00
PV8*C20 FC/MC/PC48C 1.00 1.01 1.00
P(C,V)9*C16 FC/MC/PC48C 1.00 0.94 1.01
P(C,V)9*C20 FC/MC/PC48C 1.00 0.94 1.01
P(C,V)9*D20 FC/MC/PC48D 1.00 0.94 1.01
PV8*C20 HC42 1.00 1.01 1.00
P(C,V)9*C20 HC42 1.00 0.94 1.01
PV8*C20 HD48 1.00 1.01 1.00
Continued on Page 23.