246747-YTG-L-0808
26 Johnson Controls Unitary Products
Multipliers for determining the performance with other indoor sections
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
HIGH CFM
Continued on Page 27.
COOLING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATION
OUTDOOR UNIT MODEL NO. CZE04811
INDOOR COIL MODEL NO. FC/MC60D + MV20D
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 1500 1600 1700
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 49.7 52.5 48.5 54.2 62.6 50.6 52.9 49.1 54.8 63.1 51.6 53.3 49.6 55.3 63.6
S.C. 52.8 50.4 38.3 38.5 30.4 53.8 51.3 39.7 39.7 31.3 54.8 52.2 41.1 41.0 32.3
K.W. 2.6 2.6 2.6 2.7 2.8 2.6 2.7 2.7 2.7 2.9 2.7 2.7 2.7 2.8 2.9
75
T.C. 47.4 49.9 46.0 51.7 59.5 48.3 50.4 46.5 52.2 60.0 49.2 50.8 47.1 52.7 60.4
S.C. 50.4 48.4 37.1 37.4 29.6 51.3 49.4 38.5 38.7 30.5 52.2 50.4 39.8 39.9 31.3
K.W. 2.9 3.0 2.9 3.0 3.2 3.0 3.0 3.0 3.1 3.2 3.0 3.0 3.0 3.1 3.2
85
T.C. 45.2 47.4 43.5 49.2 56.4 46.0 47.9 44.0 49.6 56.8 46.9 48.4 44.5 50.0 57.2
S.C. 47.9 46.4 35.9 36.4 28.9 48.8 47.5 37.2 37.6 29.6 49.7 48.6 38.5 38.9 30.2
K.W. 3.3 3.3 3.3 3.4 3.5 3.3 3.3 3.3 3.4 3.5 3.4 3.4 3.4 3.5 3.6
95
T.C. 42.9 44.9 40.9 46.7 53.3 43.7 45.5 41.5 47.0 53.7 44.5 46.0 41.9 47.3 54.1
S.C. 45.5 44.4 34.6 35.3 28.1 46.3 45.6 35.9 36.6 28.7 47.1 46.7 37.2 37.9 29.2
K.W. 3.6 3.6 3.6 3.7 3.8 3.6 3.7 3.6 3.8 3.9 3.7 3.7 3.7 3.8 3.9
105
T.C. 40.4 41.9 39.0 43.3 49.5 41.1 42.4 39.5 43.6 49.8 41.7 42.8 39.9 43.9 50.2
S.C. 42.8 42.1 33.9 34.0 26.7 43.4 43.0 35.0 35.3 27.3 44.1 43.9 36.1 36.5 27.9
K.W. 4.2 4.1 4.1 4.2 4.3 4.2 4.2 4.2 4.3 4.4 4.3 4.2 4.2 4.3 4.4
115
T.C. 37.9 39.0 37.2 40.1 45.7 38.4 39.4 37.6 40.4 46.1 38.9 39.8 38.0 40.6 46.3
S.C. 40.1 39.9 33.2 32.7 25.3 40.6 40.5 34.2 33.9 26.0 41.1 41.1 35.1 35.1 26.7
K.W. 4.7 4.7 4.7 4.7 4.8 4.8 4.7 4.7 4.8 4.9 4.8 4.8 4.7 4.8 4.9
125
T.C. 35.4 36.1 35.4 36.9 42.0 35.8 36.4 35.7 37.1 42.3 36.2 36.7 36.0 37.3 42.5
S.C. 37.4 37.7 32.5 31.4 23.9 37.8 38.0 33.3 32.6 24.6 38.1 38.3 34.0 33.8 25.4
K.W. 5.3 5.2 5.2 5.2 5.3 5.4 5.2 5.2 5.3 5.4 5.4 5.3 5.3 5.3 5.4
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.