York CZE04811 - Refrigerant System Data; R-410 A Charge and TXV Sizing; Refrigerant Handling Procedures

York CZE04811
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
246747-YTG-L-0808
Johnson Controls Unitary Products 3
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of intercon-
necting line tubing.
2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified on the previous page.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
evaporator + adder for line set.
Additional R-410A Charge / TXV Size for Various Matched Systems
Outdoor Unit CZE02411 CZE03611 CZE04811 CZE06011
Approved System Thermal Expansion Valve
1
1TVM(902/4F1/4A1) 1TVM(902/4F1/4A1) 1TVM(905/4J1) 1TVM(905/4J1)
Factory Charge, lbs-oz 7 - 5 8 - 4 14 - 2 13 - 9
Indoor Coil
2
TXV Kit
3
- Additional Charge, Oz
FC/MC/PC24B 2
FC/MC/PC30A 5
FC/MC/PC30B 5
FC/MC/PC36A 8
FC/MC/PC36B 8
FC/MC/PC35B 8
FC/MC/PC35C 8
FC/MC/PC42B 8
FC/MC/PC42C 8
FC/MC/PC48C 11
FC/MC/PC48D 11
FC/PC60C ––99
FC/MC/PC60D 9 9
MC61D 9 9
FC/MC62D ––99
HC36B 11
HC42 11
HC60 9 9
HD36 9
HD48 10
HD60 9 9
AV24 0–––
AV36 4–––
AV/SV48 17 9
AV/SV60 ––99
F*FV060 9 9
F*FV060H06T2C 9 9
FOOTNOTES:
1. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
2. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
3. A TXV kit must be used with these coils to obtain system performance.
Note: If a TXV is factory installed on the coil, it must be replaced with the listed TXV.