567175-YTG-E-0512
Johnson Controls Unitary Products 25
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per
degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO. CZF06013(C)
INDOOR COIL MODEL NO. FC64D
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1500 1700 1900
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 54.9 58.0 53.0 59.0 63.9 56.8 58.9 54.4 60.1 66.6 58.6 59.7 55.7 61.3 69.3
S.C. 52.0 45.1 39.2 37.3 30.2 53.5 48.2 41.0 39.5 31.8 55.1 51.2 42.7 41.8 33.5
KW 3.02 3.04 3.03 3.06 3.09 3.11 3.12 3.11 3.14 3.18 3.20 3.21 3.19 3.22 3.26
75
T.C. 51.9 54.9 50.7 56.5 61.7 53.8 55.7 52.1 57.9 63.5 55.8 56.4 53.5 59.3 65.4
S.C. 49.2 44.2 37.9 36.5 29.4 50.9 47.1 39.9 38.8 30.9 52.6 50.0 41.9 41.1 32.4
KW 3.41 3.43 3.43 3.44 3.47 3.50 3.51 3.50 3.52 3.55 3.58 3.59 3.58 3.60 3.64
85
T.C. 48.8 51.7 48.4 54.0 59.4 50.8 52.4 49.8 55.7 60.5 52.9 53.1 51.2 57.4 61.6
S.C. 46.4 43.3 36.7 35.8 28.6 48.3 46.0 38.9 38.1 30.0 50.2 48.7 41.1 40.4 31.4
KW 3.80 3.82 3.82 3.82 3.84 3.88 3.90 3.90 3.90 3.92 3.96 3.97 3.97 3.98 4.01
95
T.C. 45.7 48.6 46.1 51.5 57.2 47.8 49.2 47.5 53.5 57.4 50.0 49.8 49.0 55.5 57.7
S.C. 43.6 42.4 35.5 35.1 27.8 45.6 44.9 37.9 37.4 29.1 47.7 47.5 40.2 39.7 30.3
KW 4.19 4.21 4.22 4.20 4.22 4.27 4.28 4.29 4.28 4.30 4.35 4.35 4.36 4.36 4.38
105
T.C. 43.8 44.8 43.5 48.9 54.7 45.7 45.4 44.9 50.5 55.3 47.5 46.1 46.4 52.2 55.9
S.C. 41.7 40.1 33.7 33.8 26.4 43.5 42.0 36.2 36.0 27.7 45.3 44.0 38.6 38.2 29.0
KW 4.84 4.87 4.89 4.85 4.85 4.91 4.92 4.96 4.92 4.93 4.97 4.98 5.02 4.99 5.00
115
T.C. 42.0 41.1 41.0 46.4 52.3 43.6 41.8 42.4 47.7 53.3 45.2 42.5 43.8 48.9 54.2
S.C. 39.9 37.9 32.0 32.6 25.1 41.5 39.2 34.5 34.7 26.4 43.1 40.5 37.0 36.8 27.7
KW 5.47 5.51 5.54 5.47 5.47 5.52 5.55 5.60 5.54 5.54 5.58 5.58 5.66 5.61 5.61
125
T.C. 40.2 37.4 38.5 43.9 49.9 41.5 38.1 39.9 44.8 51.2 42.8 38.9 41.3 45.7 52.5
S.C. 38.1 35.7 30.3 31.4 23.8 39.5 36.4 32.8 33.4 25.1 40.8 37.1 35.3 35.4 26.4
KW 6.10 6.15 6.20 6.10 6.08 6.14 6.17 6.25 6.16 6.15 6.18 6.19 6.30 6.22 6.21
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Air Handlers Coils
T.C. S.C. KW
AHE60D – 1.00 1.02 0.96
AHR60D – 0.97 0.97 1.01
AV*60 – 0.98 0.97 0.96
AHX60 – 1.00 1.03 0.96
F6FP060 – 1.00 1.03 0.96
MV20D FC/MC60D 0.99 1.00 0.97
MV20D FC/MC62D 1.00 1.02 0.98
MV20D FC64D 1.02 1.04 0.94
MX20D FC/MC60D 0.99 1.00 0.95
MX20D FC/MC62D 1.01 1.03 0.95
MX20D FC64D 1.03 1.07 0.95
Furnaces Coils
T.C. S.C. KW
T*(8,L)X*C20 FC/PC60C 0.97 0.94 0.95
T*9X*C20 FC/PC60C 0.97 0.95 0.95
T*9X*D20 FC/MC/PC60D 0.98 0.97 0.94
T*(8,L)X*C20 FC/MC/PC60D 0.97 0.96 0.93
T*9X*C20 FC/MC/PC60D 0.97 0.95 0.95
T*(8,L)X*C20 FC/MC62D 0.99 0.99 0.93
T*9X*C20 FC/MC62D 0.99 0.99 0.95
T*9X*D20 FC/MC62D 0.99 0.98 0.95
T*(8,L)X*C20 FC64D 1.02 1.03 0.96
T*9X*D20 FC64D 1.01 1.02 0.95
(Y*LC/T*8V/T*LV)*C20 FC/MC62D 0.98 0.97 0.98
(Y*9C/T*9V)*C20 FC/MC62D 0.98 0.97 0.98
(Y*9C/T*9V)*D20 FC/MC62D 0.98 0.97 0.96
(Y*LC/T*8V/T*LV)*C20 FC64D 1.02 1.04 1.00
(Y*9C/T*9V)*C20 FC64D 1.01 1.01 0.99
(Y*9C/T*9V)*D20 FC64D 1.01 1.01 0.99