EasyManua.ls Logo

York D2CG180 & 240 (STY. B) - Electrical Data

York D2CG180 & 240 (STY. B)
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TABLE 6
- ELECTRICAL DATA
MODEL
POWER
SUPPLY
COMPRESSORS COND. FAN
MOTORS
(#1 & #2)
SUPPLY AIR
BLOWER
MOTOR
MINIMUM
CIRCUIT
AMPACITY
(AMPS)
MAXIMUM
TIME DELAY
FUSE SIZE
(AMPS)
#1 #2
RLA LRA RLA LRA
HP
EACH
FLA
EACH
HP FLA
DCG180
208/230-3-60 38.4 248 19.2 124 1 4.1 / 4.2 5 15.4 / 14.4 87.1 / 84.9 100
460-3-60 19.2 124 9.6 62 1 2.1 5 7.2 42.4 50
575-3-60 15.4 100 7.7 50 1 2.0 5 5.9 33.9 40
DCG240
208/230-3-60 38.4 248 38.4 248 1 4.1 / 4.2 7.5 21.0 / 19.4 115.1 / 111.6 125
460-3-60 19.2 124 19.2 124 1 2.1 7.5 9.7 55.8 60
575-3-60 15.4 100 15.4 100 1 2.0 7.5 7.8 44.8 50
VOLTAGE
LIMITATIONS**
POWER SUPPLY
VOLTAGE
MIN. MAX.
208/230-3-60 187 253
460-3-60 414 506
575-3-60 518 630
**Utilization Range A in accordance with ARI Standard 110.
530.18-N6Y
10 Unitary Products Group

Related product manuals