TABLE 6
- ELECTRICAL DATA
MODEL
POWER
SUPPLY
COMPRESSORS COND. FAN
MOTORS
(#1 & #2)
SUPPLY AIR
BLOWER
MOTOR
MINIMUM
CIRCUIT
AMPACITY
(AMPS)
MAXIMUM
TIME DELAY
FUSE SIZE
(AMPS)
#1 #2
RLA LRA RLA LRA
HP
EACH
FLA
EACH
HP FLA
DCG180
208/230-3-60 38.4 248 19.2 124 1 4.1 / 4.2 5 15.4 / 14.4 87.1 / 84.9 100
460-3-60 19.2 124 9.6 62 1 2.1 5 7.2 42.4 50
575-3-60 15.4 100 7.7 50 1 2.0 5 5.9 33.9 40
DCG240
208/230-3-60 38.4 248 38.4 248 1 4.1 / 4.2 7.5 21.0 / 19.4 115.1 / 111.6 125
460-3-60 19.2 124 19.2 124 1 2.1 7.5 9.7 55.8 60
575-3-60 15.4 100 15.4 100 1 2.0 7.5 7.8 44.8 50
VOLTAGE
LIMITATIONS**
POWER SUPPLY
VOLTAGE
MIN. MAX.
208/230-3-60 187 253
460-3-60 414 506
575-3-60 518 630
**Utilization Range “A” in accordance with ARI Standard 110.
530.18-N6Y
10 Unitary Products Group