5011492-XIM-B-0815
Johnson Controls Unitary Products 27
Table 13: Electrical Data DM 036-076
Model Power Supply
Compressors (each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Electric Heat Option
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max Fuse /
BRKR
2
Size
(Amps)
2. HACR Type per NEC.
RLA LRA MCC FLA FLA Model
3, 4
3. These electric heaters DO NOT include a fuse box. If required to meet local code, the fuse block accessory 2FB04700546 is available for
field installation.
4. Heaters are suitable for operation on 380/415-3-50 power supply
KW Stages Amps
DM036 (3)
380-3-50 7.7 58 12 1.3 2.2
NONE - - - 13.4 20
2EH04510746 4.3 1 6.5 13.4 20
2EH04511046 6.3 1 9.6 15.1 20
2EH04511546 8.5 2 12.9 19.3 20
2EH04512046 12.2 2 18.5 26.3 30
415-3-50 7.7 58 12 1.3 2.2
NONE - - - 13.4 20
2EH04510746 5.1 1 7.1 13.4 20
2EH04511046 7.5 1 10.4 16.2 20
2EH04511546 10.2 2 14.2 20.9 25
2EH04512046 14.6 2 20.3 28.5 30
DM048 (4)
380-3-50 9.6 66 15 1.3 4.24
NONE - - - 17.5 25
2EH04510746 4.3 1 6.5 17.5 25
2EH04511046 6.3 1 9.6 17.5 25
2EH04511546 8.5 2 12.9 21.4 25
2EH04512046 12.2 2 18.5 28.5 30
415-3-50 9.6 66 15 1.3 4.24
NONE - - - 17.5 25
2EH04510746 5.1 1 7.1 17.5 25
2EH04511046 7.5 1 10.4 18.3 25
2EH04511546 10.2 2 14.2 23 25
2EH04512046 14.6 2 20.3 30.7 35
DM060 (5)
380-3-50 9.6 82 14 1.3 2.7
NONE - - - 16 25
2EH04510746 4.3 1 6.5 16 25
2EH04511046 6.3 1 9.6 16 25
2EH04511546 8.5 2 12.9 19.5 25
2EH04512046 12.2 2 18.5 26.5 30
2EH04513046 18.1 2 27.5 37.8 40
415-3-50 9.6 82 14 1.3 2.7
NONE - - - 16 25
2EH04510746 5.1 1 7.1 16 25
2EH04511046 7.5 1 10.4 16.4 25
2EH04511546 10.2 2 14.2 21.1 25
2EH04512046 14.6 2 20.3 28.8 30
2EH04513046 21.5 2 29.9 40.8 45
DM076 (6)
380-3-50 8.3 45 13 1.3 2.7
NONE - - - 22.7 30
2EH04510746 4.3 1 6.5 22.7 30
2EH04511046 6.3 1 9.6 22.7 30
2EH04511546 8.5 2 12.9 22.7 30
2EH04512046 12.2 2 18.5 26.5 30
2EH04513046 18.1 2 27.5 37.8 40
415-3-50 8.3 45 13 1.3 2.7
NONE - - - 22.7 30
2EH04510746 5.1 1 7.1 22.7 30
2EH04511046 7.5 1 10.4 22.7 30
2EH04511546 10.2 2 14.2 22.7 30
2EH04512046 14.6 2 20.3 28.8 30
2EH04513046 21.5 2 29.9 40.8 45
Table 14: Electric Heat Correction Factors
NOMINAL VOLT-
AGE
VOLTAGE
kW CAP. MULTI-
PLIER
380
380 0.627
415
415 0.75
Table 15: Voltage Limitations
POWER SUPPLY
VOLTAGE
MIN. MAX.
380/415-3-50
342 456