Physical and Electrical Data - 1 Phase
MODEL
EABC-F018S EABC-F024S EABC-F030S EABC-F036S EABC-F042S EBBC-F048S EBBC-F060S
Unit Supply Voltage 208/230 – 1 – 60
Normal Voltage Range
1
187 to 252
Minimum Circuit Ampacity 11.7 14.9 18.4 21.3 30.6 31.1 42.6
Max. Overcurrent Device Amps
2
20 25 30 30 45 50 70
Compressor Type
3
Inertia Inertia Inertia Inertia Scroll Scroll Scroll
Compressor Amps
Rated Load 9.0 10.9 13.7 16 23.5 23.8 33.1
Locked Rotor 48 60 75 81 104 124 175
Crankcase Heater Yes Yes Yes Yes No No No
Fan Motor Amps Rated Load 0.5 1.3 1.3 1.3 1.3 1.3 1.3
Fan Diameter Inches 18 22 22 22 22 24 24
Fan Motor
Rated HP 1/12 1/4 1/4 1/4 1/4 1/4 1/4
Nominal RPM 1,100 850 850 850 850 850 850
Nominal CFM 1,850 3,150 3,150 3,150 3,150 3,250 3,250
Coil
Face Area Sq. Ft. 12.58 15.72 15.72 19.65 19.65 22.50 22.50
Rows Deep 1111122
Fin / Inches 13 13 13 13 13 14 14
Liquid Line OD 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Vapor Line OD 3/4 3/4 3/4 7/8 7/8 7/8 1 1/8
Unit Charge (Lbs. - Oz.)
4
5 - 13 6 - 7 6 - 9 7 - 4 7 - 1 13 - 9 12 - 11
Charge Per Foot, Oz. 0.68 0.68 0.68 0.70 0.70 0.70 0.76
Operating Weight Lbs. 142 163 167 178 180 254 262
Physical and Electrical Data - 3 Phase
MODEL
EABC-T036S EABC-T048S EABC-T060S EABC-W036S EABC-W048S EABC-W060S
Unit Supply Voltage
208/230-3-60 460 - 3 - 60
Normal Voltage Range
1
187-252 432-504
Minimum Circuit Ampacity 13.7 20.8 24.2 7.2 10.5 11.7
Max. Qvercurrent Device Amps
2
20 35 40 15 15 20
Compressor Type
3
Recip
Scroll
B
Scroll
C
Recip
Scroll
B
Scroll
C
Compressor Amps Rated
Load
9.9 15.6 18.3 5.1 7.7 8.7
Locked
Rotor
78 93 123 40 47 62
Crankcase Heater Yes No No Yes No No
Fan Motor Amps Rated
Load
1.31.31.30.80.80.8
Fan Diameter Inches 22 24 24 22 24 24
Fan Motor Rated HP 1/4 1/4 1/4 1/4 1/4 1/4
Nominal
RPM
850 850 850 850 850 850
Nominal
CFM
3,300 3,400 3,400 3,300 3,400 3,400
Coil Face Area Sq. Ft. 19.65 27.00 27.00 19.65 27.00 27.00
Rows Deep 122122
Fin / Inches 18 14 14 18 14 14
Liquid Line OD 3/8 3/8 3/8 3/8 3/8 3/8
Vapor Line OD 3/4 7/8 7/8 3/4 7/8 7/8
Unit Charge (Lbs. - Oz.)
4
9 - 5 13 - 9 12 - 9 9 - 5 13 - 9 12 - 9
Charge Per Foot, Oz. 0.68 0.70 0.70 0.68 0.70 0.70
Operating Weight Lbs. 185 240 258 185 241 258
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker.
3. All scrolls listed with a superscript “B” are Bristol scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than
15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.