571921-UTG-A-0410
Johnson Controls Unitary Products 25
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. GHGD48S41S4
INDOOR COIL MODEL NO. AHP48
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 1510 1710 1910
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 47.6 50.1 49.8 54.1 60.7 49.4 50.8 51.0 55.8 61.9 51.2 51.5 52.2 57.5 63.1
S.C. 47.6 44.7 37.8 37.0 30.4 49.4 48.3 39.9 39.3 31.5 51.2 51.5 42.0 41.6 32.6
KW 2.9 2.9 2.9 3.0 3.0 3.0 3.0 3.0 3.0 3.1 3.1 3.1 3.1 3.1 3.2
75
T.C. 45.1 46.6 46.5 50.8 56.9 46.7 47.2 47.5 52.2 58.0 48.4 47.9 48.5 53.6 59.0
S.C. 45.1 43.1 36.2 35.6 28.9 46.7 45.8 38.3 37.8 30.0 48.4 47.9 40.3 40.0 31.1
KW 3.2 3.2 3.2 3.2 3.3 3.2 3.2 3.2 3.3 3.3 3.3 3.3 3.3 3.4 3.4
85
T.C. 42.5 43.1 43.2 47.5 53.2 44.1 43.7 44.0 48.6 54.1 45.6 44.3 44.7 49.7 55.0
S.C. 42.5 41.5 34.7 34.2 27.3 44.1 43.3 36.7 36.2 28.4 45.6 44.3 38.7 38.3 29.6
KW 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.6 3.6 3.6 3.6 3.6 3.7
95
T.C. 40.0 39.6 39.9 44.2 49.4 41.4 40.2 40.4 45.0 50.2 42.8 40.7 41.0 45.8 51.0
S.C. 40.0 39.6 33.1 32.7 25.8 41.4 40.2 35.0 34.7 26.9 42.8 40.7 37.0 36.6 28.0
KW 3.6 3.6 3.6 3.7 3.8 3.7 3.7 3.7 3.8 3.9 3.8 3.8 3.8 3.9 4.0
105
T.C. 37.2 37.1 36.3 40.6 45.3 38.5 37.8 36.8 41.1 45.9 39.7 38.6 37.2 41.7 46.6
S.C. 37.2 37.1 31.6 31.3 24.2 38.5 37.8 33.5 33.2 25.2 39.7 38.6 35.4 35.1 26.3
KW 3.9 3.9 3.9 4.0 4.1 4.0 4.0 3.9 4.0 4.2 4.1 4.1 4.0 4.1 4.2
115
T.C. 34.5 34.5 32.8 36.9 41.1 35.5 35.5 33.1 37.2 41.6 36.6 36.4 33.5 37.6 42.1
S.C. 34.5 34.5 30.0 29.8 22.5 35.5 35.5 31.9 31.7 23.6 36.6 36.4 33.5 33.5 24.6
KW 4.1 4.1 4.1 4.2 4.3 4.2 4.2 4.2 4.3 4.4 4.4 4.4 4.3 4.4 4.5
125
T.C. 31.7 31.9 29.3 33.2 37.0 32.6 33.1 29.5 33.3 37.3 33.5 34.2 29.7 33.4 37.7
S.C. 31.7 31.9 28.5 28.3 20.9 32.6 33.1 29.5 30.1 21.9 33.5 34.2 29.7 31.9 22.9
KW 4.4 4.4 4.3 4.5 4.6 4.5 4.5 4.4 4.5 4.7 4.6 4.6 4.5 4.6 4.8
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handlers Coils T.C. S.C. KW
– FC/MC/PC60 0.98 0.97 1.05
– FC/MC62 0.99 0.98 1.07
– UC60 0.98 0.95 1.05
AHP48 – 1.00 1.00 1.08
AHP60 – 0.99 0.98 0.98
AHX48 – 1.01 1.01 1.00
AHX60 – 1.01 0.99 1.00
AV*48 – 1.00 0.99 0.99
AV*60 – 1.00 1.00 0.99
F4FV060 – 1.00 0.99 0.94
F5FP060 – 0.99 0.99 0.98
F6FP048 – 1.00 0.99 0.99
F6FP060 – 1.01 0.99 1.00
MV16C FC/PC60C 0.98 0.97 1.01
MV20D FC/MC60D 0.99 0.98 0.98
MV20D FC/MC62D 1.01 0.99 1.00
MA16C FC/MC60C 0.98 0.97 1.05
Furnaces Coils T.C. S.C. KW
T*(8,L)X*C16 FC/PC60C 0.99 0.98 0.98
T*(8,L)X*C20 FC/PC60C 0.99 0.98 0.98
T*9X*C16 FC/PC60C 0.99 0.98 0.98
T*9X*C20 FC/PC60C 0.99 0.98 0.98
T*9X*D20 FC/MC/PC60D 1.01 0.97 1.00
T*(8,L)X*C16 FC/MC62D 1.00 0.99 0.99
T*(8,L)X*C20 FC/MC62D 1.01 0.99 1.00
T*9X*C16 FC/MC62D 1.00 0.99 0.99
T*9X*C20 FC/MC62D 1.00 0.99 0.99
T*9X*D20 FC/MC62D 1.00 0.99 0.99
T*(8,L)X*C16 UC60C 0.99 0.96 0.98
T*(8,L)X*C20 UC60C 1.00 0.97 0.99
T*9X*C16 UC60C 0.99 0.96 0.98
T*9X*C20 UC60C 0.99 0.96 0.98
T*9X*D20 UC60D 0.99 0.95 0.98
(T*(8,L)C/T*8V)*C16 FC/PC60C 0.98 0.97 0.97
(T*(8,L)C/T*8V)*C20 FC/PC60C 0.98 0.97 0.96
(T*9C/T*9V)*C16 FC/PC60C 0.98 0.97 0.97
(T*9C/T*9V)*C20 FC/PC60C 0.98 0.97 0.97
(T*9C/T*9V)*D20 FC/MC/PC60D 0.99 0.97 0.98
(T*(8,L)C/T*8V)*C16 FC/MC62D 1.00 0.99 0.99
(T*(8,L)C/T*8V)*C20 FC/MC62D 1.00 0.99 0.99
(T*9C/T*9V)*C16 FC/MC62D 1.00 0.98 0.99
(T*9C/T*9V)*C20 FC/MC62D 0.99 0.98 0.98
(T*9C/T*9V)*D20 FC/MC62D 1.00 0.98 0.99
(T*(8,L)C/T*8V)*C16 UC60C 0.98 0.95 0.97
(T*(8,L)C/T*8V)*C20 UC60C 0.99 0.96 0.98
(T*9C/T*9V)*C16 UC60C 0.98 0.95 0.97
(T*9C/T*9V)*C20 UC60C 0.98 0.95 1.01
(T*9C/T*9V)*D20 UC60D 0.98 0.95 0.97
Furnaces Coils T.C. S.C. KW