036-21338-001-C-0703
Unitary Products Group 9
FIGURE 3 - TYPICAL FIELD WIRING WITH 7-1/2 TON FURNACE
TABLE 8: UNIT DIMENSIONS & CLEARANCES HA090
TERMINAL STRIP
TB1 ON
HA090
24-VOLT
ISOLATION RELAY
(FIELD SUPPLIED)
THERMOSTAT*
TERMINALS
TERMINAL STRIP
ON FURNACE
P-USB30N19031
*24-volt thermostat
R
Y1
B
R
Y
G
W
R
Y
G
W
C
COIL
FIELD-INSTALLED ACCESSORIES - 0° FLOW AMBIENT KITS - An auto-transformer and temperature
control maintain stable system operation by reducing the speed of the condenser fan motor.
TABLE 9: CLEARANCES
Overhead (Top)
*
*. Units must be installed outdoors. Overhanging
structures or shrubs should not obstruct con-
denser air discharge.
120”
Front (Piping and Access Panels) 30”
Left Side 24”
Right Side 24
Rear 24”
Bottom
†. Adequate snow clearance must be provided if
winter operation.
0”
http://www.rezine.ne
t
Page 11