036-21365-003-D-1105
Unitary Products Group 3
TABLE 1: ARI RATINGS
1
CONDENSING
UNIT MODEL
INDOOR BLOWER UNIT
MODEL
SYSTEM
MBH
SYSTEM EER
CONDENSING UNIT
SOUND
LEVEL
2
(DB)
HA120
LA120
126
3
10.53 88.0
1
Certified in accordance with Unitary Large Equipment certification program, which is based on ARI Standard 340/
360.
2
Rated in accordance with ARI Standard 270.
3
Deduct 1.0 MBH for units operating at 208 volts.
TABLE 2: UNIT APPLICATION DATA
Voltage Variation
1
Min. / Max.
1
Utilization range “A” in accordance with ARI Standard
110.
208/230-3-60 187 / 252
460-3-60 432 / 504
575-3-60 540 / 630
Ambient Air on Condenser Coil
Min. / Max.
35 ºF
2
/ 125 ºF
2
The minimum allowed ambient temperature for
mechanical cooling without the head pressure control
accessory installed must be raised if the indoor air flow
is less than the minimum value given in the capacity
tables.
Ambient Air on Condenser Coil
Min. / Max. with Head Pressure Control
0 - 125 ºF
TABLE 3: PHYSICAL DATA
Model
Size
(Mbh)
Compressor
1
Condenser Unit
Weight
(Lbs.)
Charge,
(Refrigerant-22)
Lbs,-Oz.
24” Fan (Propeller)
Fan Motor
2
Coil
Rating
(Tons)
Cap.
(Stg’s)
Qty.
Blades/
Pitch
(Deg.)
Nom
CFM
Pitch
(Deg.)
Qty. HP RPM Rotation**
Fins
per
inch
Rows
Deep
Ship. Oper.
Holding
3
Oper.
4
HA120 10 1 2 3/26 8100 26 2 3/4 1110 CW
20
2 731 741 2 - 0 27.85
1
Consists of one scroll compressor.
2
The ball bearing, 48 frame, single phase condenser fan motor have internal protection are directly connected to the condenser fans.
3
Holding charge is the amount in the unit as shipped from the factory.
4
Operating refrigerant charge is for the condensing unit and the matching York air handler, but does not include the charge in the
interconnecting piping.
See the Refrigerant Line Charge Table to determine the additional refrigerant charge required for interconnecting piping.
** When viewing the shaft end of the motor.