036-21365-003-D-1105
6 Unitary Products Group
TABLE 5: SYSTEM GROSS COOLING CAPACITIES AND POWER REQUIREMENTS, HF-10 WITH LF-10
(CONT.)
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
125°F
TOTAL
CAP.
1
(MBH)
TOTAL
INPUT
2
(kW)
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
CFM
WB
(°F)
86 83 80 77 74 71 68
3200
72 118 14.1 7364544536 - -
67 110 13.8 94857667584839
62 99 13.5 99968677685849
57 101 13.6 101 99 86 77 68 59 49
3600
72 120 14.2 8170604939 - -
67 113 13.9 104 93 83 72 62 52 41
62 101 13.6 101 99 94 84 73 63 53
57 103 13.7 1031029584746453
4000
72 123 14.2 8977655442 - -
67 115 14.0 1131029078675543
62 103 13.6 103 103 103 91 79 68 56
57 106 13.7 106 106 103 92 80 68 57
4400
72 124 14.3 9279665340 - -
67 116 14.0 1161059279665340
62 104 13.7 104 104 104 91 78 65 52
57 106 13.7 106 106 105 92 79 66 53
4800
72 125 14.3 9681675339 - -
67 117 14.0 1171089479655136
62 105 13.7 105 105 105 90 76 62 47
57 107 13.8 107 107 107 93 79 64 50
Nominal Rating
1 - These capacities are gross ratings. For net
capacity, deduct air blower motor, MBh =
3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air
blower motor.
2 - These ratings include the condenser fan
motors (total 1 kW) and the compressor
motors but not the supply air blower motor.