036-21338-001-C-0703
Unitary Products Group 3
TABLE 1: ARI RATINGS
*
CONDENSING
UNIT MODEL
INDOOR BLOWER UNIT
MODEL
SYSTEM
MBH
SYSTEM EER
CONDENSING UNIT
SOUND
LEVEL(BELS)
HA090
LA090 90 10.7 8.9
*. Certified in accordance with Unitary Large Equipment certification program, which is based on ARI Standard
340/360
TABLE 2: APPLICATION DATA
LIMITATION MIN. MAX.
Voltage Variation
*
208/230-3-60 187V 252V
460-3-60 432V 504V
575-3-60 540V 630V
Ambient Air on Condenser Coil
45°F
125°F
*. Rated in accordance with ARI Standard 110, utilization rangeA”.
†. Low Ambient accessories are available to permit stable system operation at ambient
temperatures down to 0°F.
Note: Refer to Form 035-15407-001 for refrigerant piping limitations
TABLE 3: PHYSICAL DATA
Model
HA
Compressor
Condenser Unit
Weight
(Lbs.)
Charge,
Lbs,-Oz.
(Refrigerant-22)
Fan (Propeller)
Fan Motor
*
Coils
Rating
(Tons)
Cap.
(Stages)
Qty.
Dia.
(in.)
Norm
CFM
Blades
Qty. RPM HP
Rotation
Face
Area‡
Finned
Length
(in.)
Rows
High
Ship. Oper. Holding
Oper.
**
Qty
Pitch
(Deg.)
090 7-1/2 1 2 24 7800 3 26 2 1110 3/4 CW 23.8
96
36 388 383 1-12 14.95
*. These PSC motors are directly connected to the condenser fans and have inherent protection, ball bearings and a 48” frame.
†. These condenser coils have 2 rows of 3/8” OD copper tubes and 16 aluminum fins per inch.
‡. When viewing the shaft end of the motor.
**. Includes matched indoor blower unit but no piping.