■ Electrical Work
NOTE
The supply voltage must be consistent with the rate voltage of the air conditioner.
■ Defrosting operation (Available for heating only).
1. Condition to start defrosting: Units will switch to defrosting
b. Unit has been running at high temperature protection
EN
mode when either of the following conditions is met.
mode* for 90 minutes. (*High temperature protection
a. Unit has been running under T3<0
o
C for 40 minutes
mode: when coil temperature of indoor unit reaches
55°C, outdoor unit will turn off external unit fan but
and T3<-3
o
C for 3 minutes.
still keep compressor running).
2. Condition to stop defrosting: Units will switch back to
Starting Defrosting Mode under condition a.
heating mode when either of the following conditions
a. Unit has been running at defrosting mode for 10
Remark: T3 is coil temperature of outdoor units.
ENGLISH 15