YORK MINISPLIT FLOOR/CEILING Code 035T80012-000
16
FLOOR/CEILING
Installation Procedure (continued)
For further detail on wiring of these units, see the diagrams
pasted inside each unit.
Cautions
Never modify the unit by removing any of the safety
guards or by bypassing any of the safety interlock
swithces.
Connect the connecting cable correctly and connect
the connecting cable to terminal as identified with their
respective marks.
Do not scratch the conductive core & inner insulator of
power supply cables and do not deform or smash on
the surface of cables.
L N 1 2
Wiring Sizes
Or as required to meet national and local codes.
Notes
Terminals N and 1 (see diagrams above) correspond
to power supply to the indoor unit coming from the
outdoor unit.
Compressor power supply is established by teminal 2.
Power supply to the 4-way valve is established by
terminal 3.
For further details on wiring of these units, see the
diagrams pasted inside each unit.
Unit size
9121825354555
Power supply mm
2
3x2.5 3x4 5x2.5 5x4
Interconnection Cooling mm
2
3x2.5 + Ground
(Indoor/Outdoor) Heating mm
2
4x2.5 + Ground
Fuse (slow-Blow) A 10 16 20 10 16
MCH/MOH 35-55 Heat pump Units
380-415V/3Ph/50Hz
460V/3Ph/60hz
Power Supply
Indoor
Unit
Outdoor Unit
N123
N
1
2
3
L
1
L
2
L
3
03_install.p65 19/4/02, 14:4816