127421-YIM-C-0606
10 Unitary Products Group
FIGURE 7 - UNIT CENTER OF GRAVITY
CLEARANCES
All units require particular clearances for proper operation
and service. Refer to Table 7 for clearances required for con-
struction, servicing, and proper unit operation.
Unit Model Number
XY
BP078
47 1/2 25 1/2
BP090
38 23
BP102
47 1/2 25 1/2
BP120
47 1/2 25 1/2
BP150
47 1/2 25 1/2
X
Y
LEFT
FRONT
Do not permit overhanging structures or shrubs to
obstruct condenser air discharge outlet, combustion
air inlet or vent outlets.
FIGURE 8 - UNIT DIMENSIONS
)RU%DVHUDLO
'LPHQVLRQV
6HH'HWDLO$
&RQYHQLHQFH
3RZHU
2XWOHW
(QWU\
3RZHU
(QWU\
&RQWURO
(QWU\
3RZHU
(QWU\
/()7
)5217
)RU'UDLQ
'LPHQVLRQV
6HH'HWDLO%
;
TABLE 6: UNIT HEIGHT
Unit Model Number
X
BP078
50 3/4
BP090
42
BP102
50 3/4
BP120
50 3/4
BP150
50 3/4
TABLE 7: UNIT CLEARANCES
Top
*
*.
Units must be installed outdoors. Overhanging struc-
ture or shrubs should not obstruct condenser air dis-
charge outlet.
72”
Right
12”
Front
36”
Left
36”
Rear
†
†.
To remove the slide-out drain pan, a rear clearance of
sixty inches is required. If space is unavailable, the
drain pan can be removed through the front by separat-
ing the corner wall.
36”
Bottom
‡
‡.
Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.
0”