FORM 160.55-O1 (604)
89
YORK INTERNATIONAL
CUSTOM VIEW SCREEN
OVERVIEW
(Flash memory Card version C.MLM.02.01 or later)
This screen allows up to 10 Service Technician se lect ed
parameters to be displayed. These parameters are se-
lect ed from a list on the Custom View Setup Screen.
This allows the Service Technician to display pa ram e ters
pertinent to a particular problem during trou ble shoot ing.
At completion of the service call, the display can be
cleared or the parameters can be left there for monitor-
ing by operations personnel.
DISPLAY ONLY
None
PROGRAMMABLE
Print
Access Level Required: VIEW
This generates a listing of the parameters displayed on
this screen.
NAVIGATION
Home
Access Level Required: VIEW
Causes an instant return to the Home Screen.
History
Access Level required: VIEW
Causes an instant return to the History Screen.
Setup
Access Level required: SERVICE
Causes a jump to the sub-screen that allows selection of
the parameters to be displayed.
FIG. 41
00375VIP
2