10 YORK INTERNATIONAL
NOTES:
See page 12 for Electrical Illustrations.
1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all other
loads included in the circuit, per N.E.C. Article 430-24. If a Factory Mounted Control Transformer is provided, add the following to the system
#1 MCA values in the YCA Tables: -17, add 10 amps; -28, add 9 amps; -46, add 4 amps; -58, add 3 amps.
2. Minimum fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs (U.L. Standard 1995, Section 36.1). It is not
recommended in applications where brown-outs, frequent starting and stopping of the unit, and/or operation at ambient temperatures in
excess of 95°F is anticipated.
3. Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit, per
N.E.C. 440-22.
4. The recommended disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the circuit,
per N.E.C. 440-12A1.
ELECTRICAL DATA
SINGLE COMPRESSOR POWER SUPPLY WIRING
(OPTIONAL)
VOLT-
DUAL MAX
INCOMING YORK
MODEL
AGE
MCA1
ELEMENT
DISC SW
SIZE
WIRE RANGE SUPPLIED DISCONNECT
YEA
CODE
FUSE SIZE
MIN SIZE4
CKT BKR
(CU ONLY)6 (CU ONLY)6,8
MIN2 MAX3 A HACR TYPE5
Z88DR6 -17 506 600 700 600 700 (1-3) #6-350MCM (1-2) #4/0 - 500MCM
Z88DR6 -28 454 500 600 600 600 (1-3) #6-350MCM (1-2) #4/0 - 500MCM
Z88DR6 -40 267 300 350 400 350 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
Z88DR6 -46 223 250 300 400 300 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J44DR7 -50 245 300 300 400 300 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
Z88DR6 -58 182 200 250 200 250 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J44DR7 -64 264 300 350 400 350 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J44DR6 -17 558 700 700 600 700 (1-3) #6-350MCM (1-2) #4/0 - 500MCM
J44DR6 -28 499 600 600 600 600 (1-3) #6-350MCM (1-2) #4/0 - 500MCM
J44DR6 -40 294 350 400 400 400 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J44DR6 -46 246 300 300 400 300 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J55DR7 -50 299 350 400 400 400 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J44DR6 -58 200 225 250 400 250 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J55DR7 -64 325 400 450 400 450 (1-3) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J44HT6 -17 558 700 700 600 700 (1-3) #6-350MCM (1-2) #4/0 - 500MCM
J44HT6 -28 499 600 600 600 600 (1-3) #6-350MCM (1-2) #4/0 - 500MCM
J44HT6 -40 294 350 400 400 400 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J44HT6 -46 246 300 300 400 300 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J55HT7 -50 199 350 400 400 400 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J44HT6 -58 200 225 250 400 250 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J55HT7 -64 325 400 450 400 450 (1-3) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J54ES6 -17 603 700 800 800 800 (1-3) #6-350MCM (1-4) #1/0 - 350MCM
J54ES6 -28 537 600 700 600 700 (1-3) #6-350MCM (1-2) #4/0 - 500MCM
J54ES6 -40 317 400 450 400 450 (1-3) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J54ES6 -46 266 300 350 400 350 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J65ES7 -50 304 350 400 400 400 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J54ES6 -58 215 250 300 400 300 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J65ES7 -64 331 400 450 400 450 (1-3) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J55HT8 -17 663 800 800 800 800 (1-3) #6-350MCM (1-4) #1/0 - 350MCM
J55HT8 -28 586 700 800 800 800 (1-3) #6-350MCM (1-4) #1/0 - 350MCM
J55HT8 -40 348 400 450 400 450 (1-3) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J55HT8 -46 294 350 400 400 400 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J66HT9 -50 323 400 400 400 400 (1-3) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J55HT8 -58 231 300 300 400 300 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J66HT9 -64 350 400 450 400 450 (1-3) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J65HT8 -17 722 800 1000 800 1000 (1-3) #6-350MCM (1-4) #1/0 - 350MCM
J65HT8 -28 637 800 800 800 800 (1-3) #6-350MCM (1-4) #1/0 - 350MCM
J65HT8 -40 380 450 500 400 500 (1-3) #6-350MCM (1-2) #2/0 - 500MCM
J65HT8 -46 319 400 450 400 450 (1-3) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J76HT9 -50 379 450 500 400 500 (1-3) #6-35oMCM (1) #1-600MCM OR (2) #1-250MCM
J65HT8 -58 252 300 350 400 350 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J76HT9 -64 411 500 500 600 500 (1-3) #6-350MCM (1-2) #4/0 - 500MCM
J66MT8 -17 769 1000 1000 800 1000 (1-3) #6-350MCM (1-4) #1/0 - 350MCM
J66MT8 -28 678 800 800 800 800 (1-3) #6-350MCM (1-4) #1/0 - 350MCM
J66MT8 -40 405 450 500 600 500 (1-3) #6-350MCM (1-2) #4/0 - 500MCM
J66MT8 -46 339 400 450 400 450 (1-3) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J77MT9 -50 424 500 500 600 500 (1-3) #6-350MCM (1-2) #4/0 - 500MCM
J66MT8 -58 269 300 350 400 350 (1) #6-350MCM (1) #1-600MCM OR (2) #1-250MCM
J77MT9 -64 460 600 600 600 600 (1-3) #6-350MCM (1-2) #4/0 - 500MCM