EasyManua.ls Logo

York RecipPak YEAJ44DR7 - Page 62

York RecipPak YEAJ44DR7
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
62 YORK INTERNATIONAL
This message indicates the number of fans on SYS 1
which were running in the reverse direction at the time of
the fault. *
This display indicates whether the Hot Gas Solenoid
Valve was energized on SYS 1 at the time of the fault.
NOTE: The micro will attempt to control the Hot Gas,
Solenoid Valve regardless of whether the option
is installed.
This message indicates whether Compressor 2 was ON
or OFF at the time of the fault.
This message indicates SYS 2 motor current at the time
of the fault.
This display shows the suction pressure of SYS 2 at the
time of the fault.
This message indicates SYS 2 discharge pressure at
the time of the fault. This display will be a fixed value
unless the Discharge Pressure Readout is installed.
This display shows the oil pressure of SYS 2 at the time
of the fault.
* The software designed to control fans whether or not they are present on the chiller as is the case on water cooled indoor units. If an indoor
unit exists, ignore this display.
This display informs the operator whether SYS 2 liquid
line solenoid was energized (ON) or de-energized (OFF)
at the time of the fault.
This message informs the operator if SYS 2 Run Per-
missive (flow switch, remote START/STOP) was in the
RUN mode (ON) or STOP mode (OFF).
This message indicates the number of stages which were
loaded on SYS 2 at the time of the fault.
This display indicates the number of fans on SYS 2 which
were running forward at the time of the fault.*
This message indicates the number of fans on SYS 2
which were running in the reverse direction at the time of
the fault. *
This display indicates whether the Hot Gas Solenoid
Valve was energized on SYS 2 at the time of the fault.
NOTE: The micro will attempt to control the Hot Gas
Solenoid Valve regardless of whether the option
is installed.
SYS 1 REVERSE FANS
OFF
SYS 1 HOT GAS VALVE
OFF
SYS 2 COMPRESSOR
OFF
SYS 2 MOTOR AMPS
60 %FLA
SYS 2 SUCT I ON PRESS
62 PSIG
SYS 2 DSCH PRESS
240 PSIG
SYS 2 O I L PRESSURE
74 PSID
SYS 2 L IQ L I NE
ON
SYS 2 RUN PERMI SS I VE
ON
SYS 2 LOADI NG STAGES
1
SYS 2 FORWARD FANS
OFF
SYS 2 REVERSE FANS
OFF
SYS 2 HOT GAS VALVE
OFF

Related product manuals