EasyManua.ls Logo

York RecipPak YEAJ55DR7 - LOCAL PRINTER OPTION

York RecipPak YEAJ55DR7
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FORM 150.60-NM4
YORK INTERNATIONAL 81
FIG. 32 WEIGH-TRONIX IMP-24 MODEL 2600
PRINTER
FIG. 33 PRINTOUT
23889A
LOCAL PRINTER OPTION
The micro panel is capable of supplying a print-out of
chiller conditions or fault shutdown information at any
given time. This allows operator and service personnel
to obtain data and system status with the touch of the
keypad. In addition to manual print selection, the micro
panel will provide an automatic print-out whenever a fault
occurs. An explanation of the keypad use to obtain a
print-out is discussed in the PRINT KEY Section on
Page 55.
YORK recommends the field tested WEIGH-TRONIX
IMP-24, Model 2600 printer. This is a compact low cost
printer that is ideal for service work and data logging.
Paper is in the form of a compact roll and is easily handled
compared to larger printers using wider business form
style paper. The paper is 2.25" wide desk-top calculator
paper that can be easily and inexpensively purchased at
most stationery stores. Shown in Fig. 32 and 33 is the
WEIGH-TRONIX printer and a typical sample print-out.
The WEIGH-TRONIX IMP-24 Model 2600 printer can be
purchased for approximately $150.00. Contact WEIGH-
TRONIX for purchase information:
Weigh-Tronix
2320 Airport Blvd.
Santa Rosa, Ca. 95402
Phone: 1-800-358-9110 or 1-707-527-5555
(International Orders Only)
NOTE: The print-out is made to be universal to all types
of chillers both air and water cooled with or with-
out options. Items may be indicated on the print-
out which may not be present on the chiller.
YORK INTERNATIONAL CORPORATION
RECIPROCATING WATER CHILLERS
SYSTEM STATUS
8:45AM 4/17/95
SYS 1 COMPRESSOR RUNNING
SYS 2 ANTI-COIN TIMER 13 SEC
RETURN WATER TEMP 65.0 DEGF
LEAVING WATER TEMP 54.0 DEGF
LOW WATER CUTOUT 36.0 DEGF
SETPOINT TEMP 45.0 DEGF
OUTSIDE AIR TEMP 75.0 DEGF
LOW AMBIENT CUTOUT 10.0 DEGF
LOW PRESSURE CUTOUT 44 PSIG
LEAD SYSTEM SYS 1
CONTROL TYPE LCHWT
COOLING RANGE 45.0 TO 47.0 DEGF
SYSTEM 1 DATA
COMPRESSOR STATUS ON
MOTOR AMPS 5 0 %FLA
SUCTION PRESSURE 61 PSIG
DISCHARGE PRESSURE 143 PSIG
OIL PRESSURE 75 PSID
LIQUID LINE SOLENOID OFF
RUN PERMISSIVE ON
STAGES OF LOADING 1
FORWARD FANS OFF
REVERSE FANS OFF
HOT GAS BYPASS VALVE OFF
SYSTEM 2 DATA
COMPRESSOR STATUS ON
MOTOR AMPS 0 %FLA
SUCTION PRESSURE 61 PSIG
DISCHARGE PRESSURE 80 PSIG
OIL PRESSURE 1 PSID
LIQUID LINE SOLENOID OFF
RUN PERMISSIVE ON
STAGES OF LOADING 1
FORWARD FANS 1
REVERSE FANS OFF
HOT GAS BYPASS VALVE OFF
S M T W T F S *=HOLIDAY
SUN START=06:00AM STOP=11:00AM
MON START=06:00AM STOP=11:00AM
TUE START=06:00AM STOP=11:00AM
WED START=06:00AM STOP=11:00AM
THU START=06:00AM STOP=11:00AM
FRI START=06:00AM STOP=11:00AM
SAT START=06:00AM STOP=11:00AM
HOL START=00:00AM STOP=00:00AM