REPLACEMENT DEMAND DEFROST CONTROL BOARD S1-33101975102
FOR USE WITH MODELS: 12, 13 & 14 SEER HEAT PUMPS
REPAIR PART KIT INSTALLATION INSTRUCTIONS
Subject to change without notice. Printed in U.S.A. 035-21270-001-A-0906
Copyright © by York International Corp. 2006. All rights reserved. Supersedes: Nothing
Unitary 5005 Norman
Product York OK
Group Drive 73069
INSTALLATION
1. Power off unit totally - 240V & 24V.
2. Carefully record positions and colors of wiring removed.
3. Remove old defrost circuit board.
4. Install replacement circuit board - utilizing same placement,
mounting & screws.
5. Refer to unit Installation Manual or Table 1 below - and set
the Demand Defrost Curve Selection Jumper to the proper
position. For the new jumper setting to take effect - all 24V
power to the board must be removed and reapplied.
6. Complete the installation and power up the unit, re-apply-
ing both 240V & 24V.
DEFROST CURVE SELECTION
When the control board is replaced, the jumper MUST be
placed in a numbered position. Select the proper jumper posi-
tion from Table1. If the jumper is missing or in the P posi-
tion, the replacement control will not energize the
compressor.
When the jumper position is changed, the control will not act
upon the jumper changes until the thermostat calls are de-ener-
gized or power (24 VAC) to the control is cycled.
The control will display the active defrost curve using the X/L
terminal when the heat pump is operating in a defrost cycle that
has been forced using the TEST inputs. For instance, the X/L
output will be energized with two flashes when defrost curve 2
is active. The control only reads the jumper input when the Y
and W thermostat inputs are de-energized.
FIGURE 1: Outdoor Unit Control Box FIGURE 2: Demand Defrost Control Module
HEATER LIMIT SWITCH
(Not on all Units)
DUAL
RUN/FAN
CAPACITOR
GROUND
LUG
CONTACTOR
DEFROST
CONTROL
BOARD
“FINGERED”
BUSHING
LOW
VOLTAGE
BOX
REVERSIBLE HIGH
VOLTAGE CONDUIT PLATE
START
CAPACITOR
(Not on all Units)
START RELAY
(Not on all Units)
TEST
AMBIENT
AMBG
COIL G
COIL
1
2
3
4
COND
FAN
HIGH VOLTAGE
PRESSURE
M
SWITCH
REV
VALVE
X/L
R
C
Y
O
W
W1/66
X/L
R
C
Y
O
W
W1/66
DEMAND
DEFROST CURVE
SELECTION JUMPER
P
TABLE 1: Defrost Initiate Curves
Defrost Curve Selection
Jumper Position
1234
14 Seer 2, 3, 4 Ton 2.5, 3.5 Ton None None
All Other Models All None None None
Question and Answer IconNeed help?

Do you have a question about the York S1-33101975102 and is the answer not in the manual?

York S1-33101975102 Specifications

General IconGeneral
BrandYork
ModelS1-33101975102
CategoryComputer Hardware
LanguageEnglish

Summary

Installation Procedures

Power Off Unit

Turn off all 240V and 24V power to the unit before proceeding.

Record Wiring Connections

Carefully document the positions and colors of all removed wiring.

Remove Old Circuit Board

Disconnect and remove the existing defrost circuit board.

Install Replacement Circuit Board

Mount the new circuit board using the same placement and hardware.

Set Demand Defrost Curve Jumper

Refer to installation manual or Table 1 to set the jumper to the correct position.

Complete Installation and Power Up

Finish the installation and reapply both 240V and 24V power to the unit.

Defrost Curve Selection

Jumper Position Impact

If jumper is missing or in 'P', the control will not energize the compressor.

Jumper Change Activation

Control acts on jumper changes only when thermostat calls are de-energized.

Defrost Curve Initiation Table

Table 1 details defrost curve selection based on Seer rating and tonnage.

Active Defrost Curve Display

The X/L terminal displays the active defrost curve during a defrost cycle.