TABLE 22: SUPPLY AIR BLOWER PERFORMANCE (BP072 BELT DRIVE) - SIDE DUCT APPLICATION
Air
Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive Standard Drive Option HIgh Static Drive Option
1600 795 0.60 878 0.67 958 0.74 1035 0.82 1108 0.91 1179 1.00 1247 1.09 1313 1.19 1376 1.28 1438 1.39
1800 836 0.72 919 0.79 999 0.87 1075 0.95 1149 1.03 1220 1.12 1288 1.22 1353 1.31 1417 1.41 1478 1.51
2000 880 0.89 963 0.96 1042 1.04 1119 1.12 1193 1.20 1263 1.29 1331 1.39 1397 1.48 1460 1.58 1522 1.68
2200 926 1.10 1009 1.17 1089 1.25 1166 1.33 1239 1.41 1310 1.50 1378 1.60 1444 1.69 1507 1.79 1568 1.89
2400 976 1.35 1059 1.42 1138 1.50 1215 1.58 1289 1.66 1359 1.75 1428 1.85 1493 1.94 1557 2.04 1618 2.14
2600 1028 1.64 1111 1.71 1190 1.78 1267 1.87 1340 1.95 1411 2.04 1479 2.13 1545 2.23 1608 2.33 1670 2.43
2800 1082 1.96 1165 2.03 1244 2.11 1321 2.19 1394 2.27 1465 2.36 1533 2.46 1599 2.55 1662 2.65 1724 2.75
3000 1138 2.32 1221 2.39 1300 2.47 1377 2.55 1451 2.63 1521 2.72 1589 2.81 1655 2.91 1718 3.01 1780 3.11
Field Supplied Drive
TABLE 23: SUPPLY AIR BLOWER PERFORMANCE (BP072 BELT DRIVE) - BOTTOM DUCT APPLICATION
Air
Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive Standard Drive Option HIgh Static Drive Option
1600 789 0.60 880 0.67 967 0.74 1050 0.82 1130 0.91 1207 0.99 1282 1.08 1353 1.18 1422 1.27 1489 1.37
1800 833 0.73 924 0.80 1011 0.87 1094 0.95 1174 1.03 1251 1.12 1326 1.21 1397 1.30 1466 1.40 1533 1.50
2000 881 0.89 971 0.96 1058 1.03 1142 1.11 1222 1.20 1299 1.28 1373 1.37 1445 1.47 1514 1.57 1580 1.66
2200 932 1.10 1022 1.17 1109 1.24 1193 1.32 1273 1.40 1350 1.49 1424 1.58 1496 1.67 1565 1.77 1631 1.87
2400 986 1.34 1076 1.41 1163 1.48 1246 1.56 1327 1.64 1404 1.73 1478 1.82 1550 1.92 1619 2.01 1685 2.11
2600 1042 1.62 1132 1.69 1219 1.76 1303 1.84 1383 1.92 1460 2.01 1534 2.10 1606 2.20 1675 2.29 1742 2.39
2800 1101 1.94 1191 2.00 1278 2.08 1362 2.15 1442 2.24 1519 2.33 1593 2.42 1665 2.51 1734 2.61 1800 2.71
3000 1162 2.28 1252 2.35 1339 2.42 1423 2.50 1503 2.59 1580 2.67 1654 2.76 1726 2.86 1795 2.96 1862 3.05
Field Supplied Drive